Reference GPU Pod — DCIM Model & Commissioning Package

build docs

Every code push rebuilds both pods from an empty NetBox and re-runs the exports; every push, documentation included, asserts that the figures quoted below are the ones those exports contain. The badges are the claim that the numbers on this page are reproduced rather than remembered.

NetBox models of two NVIDIA DGX SuperPOD scalable units, built from published reference architecture, with one generator that reproduces either from a YAML spec:

Site Design Spec
Reference Pod 1 32× DGX H100, air-cooled, 12 racks, 359.6 kW spec/pod.yaml
Reference Pod 2 8× GB200 NVL72, liquid-cooled, 9 racks, 977.2 kW spec/pod-gb200.yaml

Scope honesty. This is a design and documentation exercise: a paper model of a published reference architecture. Nothing here was deployed or operated, and it is not affiliated with NVIDIA. Figures are labelled sourced or assumed throughout, and the distinction is kept deliberately visible.

Status: both pods converge. 21 racks, 406 devices, 1,314 cables, 1,336.8 kW. Each rebuilds from its own spec by running one script, and a run over either reconciles the objects they share to identical values.

Rack elevations across the pod

Compute racks repeat NVIDIA's published profile — rPDUs at U42–47, DGX at U30, U22, U11 and U3, with the 3U airflow gap at U19–21. N01/N02 hold the eight leaf and four spine switches, M01 the UFM pair and management fabric, S01 the storage nodes.


What's here

Path Contents
spec/pod.yaml Air-cooled H100 pod — the desired end state
spec/pod-gb200.yaml Liquid-cooled GB200 NVL72 pod
scripts/build_pod.py Idempotent generator; reconciles NetBox against a spec
scripts/netbox_client.py Shared connection helper (handles both NetBox auth schemes)
scripts/check_connection.py Preflight — verifies reachability and write scope
scripts/show_choices.py Prints the type slugs the live instance accepts
scripts/show_cooling.py Prints NetBox 4.7's cooling model as this instance serves it
scripts/clear_busbar_cables.py Narrow deletion tool — the generator never deletes
scripts/export_reports.py Power reports, cable schedules, rail map, cooling, comparison
docs/design-notes.md What is sourced, what is a choice, what is a guess
docs/methodology.md How the generator got from get-or-create to reconciling
docs/roadmap.md What is done, what is left, and what was rejected
docs/commissioning-checklist.md Site readiness through handover
exports/ Generated CSVs, one set per pod, plus pod-comparison.csv
env-example/ .env and compose override to copy into netbox-docker/

Running it

git clone https://github.com/netbox-community/netbox-docker.git
cp env-example/.env env-example/docker-compose.override.yml netbox-docker/
cd netbox-docker && docker compose up -d
docker compose exec netbox /opt/netbox/venv/bin/python /opt/netbox/netbox/manage.py createsuperuser

NetBox comes up on http://127.0.0.1:8000/ — bound to loopback deliberately, since the upstream example publishes on all interfaces. Pinned to NetBox v4.7 via netbox-docker 5.1.0, Postgres 18, Valkey 9.1.

Then create an API token in the UI and:

python3 -m venv .venv && source .venv/bin/activate
pip install -r requirements.txt
printf 'NETBOX_URL=http://127.0.0.1:8000\nNETBOX_TOKEN=<your token>\n' > .env
python scripts/check_connection.py
python scripts/build_pod.py --dry-run
python scripts/build_pod.py

For the liquid-cooled pod, point it at the other spec:

python scripts/build_pod.py --spec spec/pod-gb200.yaml --dry-run
python scripts/build_pod.py --spec spec/pod-gb200.yaml
python scripts/export_reports.py

build_pod.py is idempotent — run it as often as you like. It reads current state fresh each time rather than tracking what previous runs did, so an interrupted run is fixed by running it again, with no cleanup step. The two specs live in separate sites and share a region and several device types; running either reconciles those shared objects to the same values, which is a check on both files.


Reference Pod 1 — the air-cooled SU

12 racks in one scalable unit:

Racks Role Contents
C01–C08 Compute 4× DGX H100 at U3/U11/U22/U30, 3× rPDU at U42/44/46
N01–N02 Network 8× QM9700 compute leaf, 4× spine, storage fabric
M01 Management UFM pair, SN4600C in-band, SN2201 out-of-band
S01 Storage Storage nodes and storage fabric leaf

Sourced figures

Value
DGX H100 8U, 10.2 kW, 130.45 kg, 6 PSUs in 4+2 user guide
8× NDR400 InfiniBand per system components
Scalable unit up to 32 DGX H100; 8 leaf + 4 spine architecture
Rack density 4 systems/rack → >40 kW/rack architecture
Racks EIA-310, ≥48U, 800×1200 mm recommended electrical
Power scheme 415 VAC, 60 A, 3-phase, N+1, ≥3 sources/rack electrical
each source sized for 50% of peak load electrical
QM9700 1U, 64× NDR400, 747 W passive / 1720 W active QM97x0 specs
SN4600C 2U (88 mm), 64× QSFP28 100GbE, 466 W SN4000 specs
SN2201 1U, 48× 1GbE + 4× QSFP28, 98 W SN2201 specs
UFM appliance 2U (88 mm), 2 PSUs, InfiniBand + OOB ethernet UFM specs
Rack profile servers from U3, 3U airflow gap, horizontal rPDUs at top infrastructure

Assumed, not sourced

Storage node model and count, the 2 storage + 2 in-band NICs per DGX, SN2201 dual PSU, UFM power draw, rPDU height, and all cable lengths. Full list with reasoning in docs/design-notes.md.

That file also separates what NVIDIA prescribes from what it explicitly leaves open. The compute side is specified in detail; the management-rack figure carries the caveat that "sizes and quantities will vary depending upon models used." The infrastructure choices here are choices, and are labelled as such rather than presented as conformance.


Design decisions

Fuller reasoning, and the line between what NVIDIA specifies and what it leaves open, in docs/design-notes.md.

Leaf switches end-of-row, not top-of-rack. Rail-optimised topology requires rail n from all 32 nodes to land on the same leaf, which makes ToR structurally impossible. This is also what brings the 30 m InfiniBand guidance into play.

leaf-04 downlinks and uplinks

Rail-optimised, made concrete. Every one of leaf-04's 32 downlinks is some node's ib-rail3 — dgx-c08-04 on port 32, seven racks away from dgx-c01-01 on port 1. Uplinks start immediately at port 33, so all 64 ports are consumed: 32 down, 32 up.

QM9700 budgeted at 1720 W, not 747 W. NVIDIA publishes 747 W with passive cables; end-of-row placement exceeds passive copper reach, so this pod runs optical and the active-cable maximum is the honest number. The topology decision propagates directly into the power budget.

Three power sources per rack, not an A/B pair. Four DGX H100 at peak draw 40.8 kW, but no single circuit option in NVIDIA's table exceeds 32.8 kW. That gap is why the guide specifies a minimum of three sources at 50% sizing rather than two.

800 mm cabinets, not the 600 mm minimum. With 8 NDR400 rails per node plus storage, in-band, out-of-band and three power feeds, 600 mm is impractical — and 800 is NVIDIA's own recommendation.

Power modelling rule. allocated_draw = total ÷ PSU count (normal operation); maximum_draw = total ÷ PSUs required (worst case). For the DGX H100's 4+2 that is 1700 W and 2550 W per supply. Budget against allocated; size circuits against maximum.

UFM InfiniBand ports left uncabled. A strictly 1:1 non-blocking fabric consumes every port — 32 down and 32 up per leaf, and 8 leaves × 8 links fills all 64 spine ports — so there is nowhere to attach a management appliance. Real deployments reserve fabric ports for this at the cost of slight oversubscription. Inventing a free port would have produced a model that looks complete while quietly breaking the property the topology exists to provide.


Results — Reference Pod 1

From exports/h100-*.csv, regenerated by scripts/export_reports.py:

Pod load 359.6 kW, 91% of it GPU
Compute rack, steady state 13,600 VA of 34,501 VA per feed — 39.4%
Compute rack, one source lost 20,400 VA per feed — 59.1%, N−1 PASS
Network racks ~10% — the fabric is not the constraint
Cables 970, none exceeding the 50 m optical limit
Rail map 8 rails, one leaf each, 32 nodes each — all PASS

Power feed utilisation on a compute rack

One of C05's three feeds. 13,600 VA drawn of 34,501 VA available — computed by NetBox from the actual cable path: feed → rPDU input → outlet → PSU.

The N−1 figure is the validation. On loss of one of three sources each survivor carries 20.4 kW — NVIDIA's published peak-server-demand-per-circuit figure, reached independently by walking the model's own cable topology rather than copied from the document.

One discrepancy, reported rather than smoothed over: NetBox computes the 415 V / 60 A three-phase feed at 34,501 VA; NVIDIA's electrical table lists the same circuit at 32.7 kW. About 5%, from a different derating assumption. It does not change the N−1 verdict — every rack passes against either figure — but it should be resolved against a facility's own standard before anything is ordered.



Reference Pod 2 — the liquid-cooled SU

8× GB200 NVL72 plus a CDU rack, in a separate site so the air-cooled pod stays intact as the reference. 314 devices, 344 power cables, and a three-tier cooling topology built on NetBox 4.7's native cooling objects.

G01 and C01 elevations side by side

The same 48U cabinet, the same Compute rack role. C01 holds four 8U DGX H100 — 32 GPUs at 40.8 kW — with the 3 RU airflow gap at U19–21 that NVIDIA's published rack profile specifies. G01 holds 18 one-rack-unit compute trays, nine NVLink switch trays and eight power shelves: 72 GPUs at 119.7 kW. G01's layout is invented, because NVIDIA lists what an NVL72 contains and never says where any of it sits — the free band at U36–46 is a consequence of that, not a design feature. The one thing both racks do agree on is management at the top: C01's rPDUs at U42/44/46, G01's ToR switches at U47/48.

From exports/pod-comparison.csv. Compute racks only — Pod 2 has no network or management racks modelled yet, so a whole-pod count would flatter it:

H100 GB200
GPUs 256 576 2.25×
GPUs per compute rack 32 72 2.25×
kW per compute rack 40.8 119.9 2.94×
kW per GPU 1.275 1.665 1.31×
Compute racks per 1,000 GPUs 31.2 13.9 0.45×
Feeds per compute rack 3 8 2.67×
Redundancy N+1, three sources at 50% N+N, two sides at 100%
Worst surviving feed 59.1% 86.7% 1.47×

The headline is the trade, not the density. The same GPU count needs 56% fewer racks and 31% more power to run them — the energy is concentrated, not saved — while the electrical margin after the worst credible loss narrows from 59% to 87%.

What changes in the power model

AC/DC conversion moves into the rack. Pod 1 is feed → rPDU → outlet → PSU. The NVL72 is feed → power shelf → 50 V DC busbar → tray: four hops, and the tray has no PSU redundancy of its own because all of it moved upstream.

A busbar is not a tree. NetBox models power as one-to-one cables; a busbar is one shared plane that eight shelves push into and twenty-seven trays pull from. It is modelled as 8 inputs and 32 outlets divided four apiece, and that division is fiction — chosen so the totals aggregate, saying nothing true about which shelf carries which tray.

busbar-g01 power utilisation per input

The eight busbar inputs, four trays each. 16,200 / 15,800 / 13,300 VA is as close as a one-to-one cable tree gets to a shared bus, where every shelf would carry 14,962 — the residual spread is an artefact of 27 discrete trays not dividing into 8, not a property of the design. Note the empty Available and Utilization columns: the input ports declare no maximum draw, deliberately, since that is precisely what lets NetBox aggregate what is plugged in. A first version of the allocator dealt trays round-robin over a name-sorted list and put 18,700 VA on shelf 1 — a hotspot invented by alphabetical order.

So the N+N verdict is asserted, not derived. Pod 1's 20.4 kW N−1 figure counted as independent reproduction because NetBox walked the cable path. Nothing equivalent exists here, and the report says so rather than borrowing the credibility of the first result.

What NetBox 4.7's cooling model does and doesn't do

It ships real cooling objects — sources, feeds, and intake/outflow components that parent exactly like power outlets do. The CDU and rack manifold are built the same way an rPDU is, and the same silent-failure trap applies.

But it carries capacity at every level and demand at none, and there is no cable or foreign key joining a feed to a device. It will hold a complete, correct topology and compute nothing from it. Every cooling figure in exports/gb200-cooling-report.csv is therefore derived by this repo from the power model, and every row carries a basis column saying so.

Two of the 226 cooling intakes can never be wired — the CDUs' facility-water side, where the model has no link to express. The report separates unwired_at_plant from unwired_unexplained for that reason.

Rack X01, the CDU rack

X01, holding the two CDUs. Cooling capability is set and cooling capacity is blank — NVIDIA publishes no figure, and an invented one produces a PASS that was never earned; an earlier version set it to the rack's published power draw and the report duly compared a number against itself. Two cooling feeds attach here, which is the only association NetBox can express between facility plant and the equipment it serves. Power utilisation reads 0.0% because the CDUs' 18 kW is one of the named gaps below — it appears in the power report's uncabled_w column rather than being quietly given a circuit that was never designed.

Named gaps

19,568 W appears in the power report's uncabled_w column: ToR switch power (NVIDIA says the racks contain them and not what powers them) and CDU power (no distribution modelled in the CDU rack yet). Network and management racks and fabric cabling are not modelled, pending sourced switch counts. Full list, with the much longer GB200 assumption set, in docs/design-notes.md.


Notes on NetBox itself

Two behaviours that cost real time, recorded because they aren't obvious:

A pass-through power port aggregates downstream load only when both maximum_draw and allocated_draw are empty. Setting maximum_draw on an rPDU's input makes NetBox use the declared value instead of computing from what's plugged in, so the feed reads 0 VA behind a perfectly healthy "Reachable" cable. Supplying more data breaks the calculation.

Power outlets must have their parent power port set, or there is no path from a device PSU up to the feed. Fails the same silent way. The 4.7 cooling model repeats this exactly: a cooling outflow parents to a cooling intake the way an outlet parents to a power port, and an unparented one is just as invisible.

Rack cooling capability and capacity are inherited from the rack type. A per-rack value is accepted, returns 200, and is discarded — so a generator can report updated: 1 while nothing changed, and report it again on every run afterwards. Two racks of the same cabinet model therefore cannot differ in cooling capacity, even though that depends on what is installed rather than on the cabinet.

Also worth knowing: the REST API does not expand [1-64] name ranges — that is a UI-form feature only. And NetBox 4.7 issues nbt_<key>.<token> credentials requiring the Bearer scheme rather than pynetbox's default Token.