Ferroamp Control for Home Assistant

A writable control driver for the Ferroamp Energy Hub that implements the EMS inverter contract so it can be orchestrated by ha-ems (EMS Steward). It exposes the mode selector and battery power setpoint and actuates the hub over its local MQTT ExtAPI.

Status — v0.2 (MQTT ExtAPI, control OFF by default, hub answers paired)

The driver is implemented against Ferroamp's local MQTT ExtAPI. It publishes charge / discharge / auto commands to <base_topic>/control/request (requires the ExtAPI / EMS option to be enabled on your hub).

Safety first — nothing reaches the battery until you opt in:

  1. A per-entry switch.ferroamp_control_enabled defaults OFF. While off, the driver builds no command and publishes nothing.
  2. EMS ships in read-only mode, so it won't even write to these entities until you disable its read-only switch.

So you can install, configure and wire everything up, watch what EMS would send in the logs, and only flip control on once you trust it.

Telemetry (SoC, powers, capacity) still comes from the existing read-only ferroamp MQTT integration — install this driver alongside it. This driver provides only the writable surface.

Verify against your hub before enabling control

  • Base topic — default extapi; commands go to extapi/control/request. Confirm your hub's ExtAPI topic (some setups namespace it differently).
  • Command format — {"transId": "<uuid>", "cmd": {"name": "charge", "arg": "<watts>"}}, discharge likewise, auto to hand back. Confirm against your ExtAPI documentation.
  • With control still OFF, set number.ferroamp_battery_power_setpoint manually and check the log line Ferroamp control → … shows the payload you expect.

Inverter contract (entities exposed)

Entity Purpose
switch.ferroamp_control_enabled Master gate — OFF by default
select.ferroamp_mode self_consumption, peak_shaving, forced_charge, forced_discharge, idle
number.ferroamp_battery_power_setpoint W, ± (charge / discharge → ExtAPI command)
number.ferroamp_grid_power_limit W, advisory peak cap (peak shaving realised via setpoint)
sensor.ferroamp_last_command idle / pending / ack / nak: the hub's answer to the latest command, with last_command (and in it refreshed_at once the command has been sent again), last_ack, last_nak, last_result as attributes
binary_sensor.ferroamp_following on = the hub acknowledged the latest command, off = it refused it (NAK); EMS raises a Repairs issue after two ticks of NAK

Telemetry sensors (sensor.ferroamp_soc, _battery_power, _grid_power, _solar_power, _battery_capacity) are consumed by EMS directly from the ferroamp telemetry integration and are not re-published here.

See custom_components/ems/inverter_contract.py in the EMS repo for the authoritative contract definition.

The hub answers back (0.2.0)

Every command carries a transId; the hub answers on <base_topic>/control/response (receipt: ack "sending cmd to ESOs", or nak, typically "transaction in progress") and on <base_topic>/control/result (outcome: "all ESOs have changed setting"). The driver subscribes to both, pairs the answers with what it sent and shows the verdict on sensor.ferroamp_last_command and binary_sensor.ferroamp_following. A NAK is logged as a warning. Answers to transactions the driver did not send (another app or integration commanding the same hub) are ignored and counted in the unmatched attribute, which is the quickest way to see that something else is talking to the hub. A command the hub refused is published again on the next write even when the setpoint is unchanged (0.2.1); EMS Steward 0.30's recovery from a NAK depends on it.

A standing command is sent again (0.3.6)

The hub can drop an ExtAPI command without a word: when a slot of its own schedule in the Ferroamp portal begins, or when its portal settings change, it goes back to its own logic, sends no NAK, and binary_sensor.ferroamp_following stays on. Until 0.3.5 the driver published only when the command changed, so the hub could stay on its own logic for hours while the setpoint said charge or hold. The same command sent again takes the battery back within half a minute, so a charge or discharge that has stood for five minutes (REFRESH_S, 300 s) is now published again:

  • with the next write of the setpoint. EMS writes it on every tick, so with its default five-minute tick each tick sends a standing charge or hold again, as that tick's one transaction.
  • from the driver's own timer when nothing writes: EMS stopped without handing the hub back, a setpoint set by hand, or EMS ticking less often than every five minutes. The timer fires five and a half minutes after the last write and then every five minutes, which keeps it half a minute off EMS's whole-minute ticks. The hub needs about ten seconds to apply a command and refuses one that arrives meanwhile ("transaction in progress"), so a refresh just ahead of EMS's next, changed command would cost that command a tick.

auto is never sent again: re-sending it makes the hub re-ramp its self-consumption. A refresh waits while a transaction is still open (sent, no result yet), so refreshes cannot pile NAKs onto the hub, and a NAK is handled as before: the command is forgotten and the next write sends it. A refresh keeps the hub's verdict until the hub answers it, so binary_sensor.ferroamp_following does not blink, and last_command keeps the time the command was given, with the latest repeat as refreshed_at. Switching control off, or unloading the entry, stops the timer, an unload for good even while a publish is still on its way to the broker; after a restart it starts with the first command. While a charge or hold stands that is one more transaction every five minutes, at most 288 a day.

Roadmap

  • A test that holds the report to stats.py's key list. stats.py passes only the keys in its EXTRA_KEYS on; anything else stats_extra builds is dropped without a word. Read EXTRA_KEYS from stats.py and check that every key the report builds is in it, so a dropped key fails locally. (The shared file itself was synced from ha-ctc in 0.3.3.)
  • Modbus TCP transport as an alternative to MQTT, once a verified Ferroamp register map is available (the config flow is structured to add it).

Why a separate plugin?

Brand-specific control logic doesn't belong in the brand-agnostic EMS. Each inverter family gets its own driver repo; users install the driver matching their hardware. Future siblings:

  • ha-solaredge-control
  • ha-huawei-control
  • ha-victron-control

Disclaimer

Not affiliated with Ferroamp AB.

Anonymous statistics

The driver sends one report per day to https://stats.rnet.se: which version you run, your Home Assistant version and installation type, the country you have set in Home Assistant, an approximate position rounded to about 11 km, the battery power it is allowed to command, whether control is enabled and has actually been used, whether the grid limit is in use, and how many commands the hub refused since the last report.

No power readings, no energy, no time series: this driver commands a hub, it does not meter a house. It never sends a name, an address, an exact position, a serial number, an MQTT topic or an entity name, and your IP address is not stored. The refusal count is the one number that says whether the driver actually works in the field, which is exactly what a maintainer cannot see from one installation.

To opt out: Settings, Devices and services, Ferroamp Control, Configure, Send anonymous usage statistics. Switching it off also erases what has already been sent. The full list of fields and the reasoning: https://stats.rnet.se/integritet.

License

Apache License 2.0, see LICENSE.