Autonomous filtration pump controller for APA Devices pool automation
·
·
- PCF8574AT I2C relay expander (default) or direct Arduino GPIO — one constructor covers both
- Non-blocking state machine: IDLE → STARTING → RUNNING → STOPPING
- Safe boot: all relays start OFF regardless of previous relay or pin state
- Manual override:
FORCE_ON,FORCE_OFF,AUTO— with optional timeout or midnight auto-return - Extension relay outputs on PCF P4–P7 for lights or extra equipment
- Schedule callback drives pump on/off without any external library
- Daily runtime target with catch-up logic and optional time window
- Midnight rollover via RTC epoch callback or 24-hour millis() fallback
- UVC sanitizer — ON before pump, OFF after (configurable pre/post delay)
- AUX device (heat pump, ozone, etc.) — ON after pump, OFF before pump stops
- Solar valve — opens when solar drives the pump; instantly closes in manual mode
- Absorber–pool temperature dead-band hysteresis (configurable start/stop deltas)
- Pool cooling: runs in reverse when pool temperature exceeds maximum
- Day/night boundary gate via RTC epoch callback
- Solar safety (Priority 0): absorber too hot → pump ON + valve OPEN, overrides even
FORCE_OFF
- Overcurrent — EMA-learned baseline × 1.5 threshold; cold-start gate of 5 samples
- Dry-run — pressure below EMA baseline × 40% (or absolute minimum before EMA builds)
- Overpressure — absolute hard limit at
maxPressureAND EMA-relative dirty-filter detection - Freeze protection — pool temp below 4.5 °C → cyclic run (5 min ON / 10 min rest); suppressed if dry-run detected
- No-flow stub — flow switch confirmed after settle; hardware-ready for future sensor
- All alarms are latching — explicit
acknowledgeAlarm()required
- 564 B SRAM on Arduino Uno with all features registered — fits comfortably in 2 KB
- 23 boolean flags packed into 3 bytes; all string literals in flash (
F()macro) - EEPROM: 12 bytes, magic + version + checksum validation, persists target and clean pressure
- Zero
delay()calls — every path returns within oneloop()iteration - Designed to integrate with APADOSE and APALCDGUI via callback bridges — no coupling
Arduino IDE: Sketch → Include Library → Add .ZIP Library → select the APAPUMP folder.
PlatformIO:
lib_deps =
https://github.com/apadevices/APAPUMPAPAPUMP controls a pool filtration pump and up to three follower devices (UVC lamp, AUX device, solar valve) through a PCF8574AT I2C relay expander or direct Arduino output pins. Each call to update() in your loop() advances the state machine, checks every safety guard in priority order, and fires alarm callbacks when something is wrong — all without blocking.
Out of the box, the zero-arg constructor targets the APA Devices HMI board v1.0: PCF8574AT at 0x3C with pump on P0, UVC on P1, AUX on P2, and solar valve on P3. Every optional feature is disabled by default and activated with one method call.
┌──────────────────────────────────┐
│ pump.begin() │
▼ │
[ IDLE ] │
│ │
_shouldPumpRun() = true │
min OFF time OK (60 s) │
│ │
[ STARTING ] │
│ │
UVC pre-delay (default 5 s) │
│ │
[ RUNNING ] ◄── safety alarms checked: │
│ current · pressure · │
│ flow · freeze │
_shouldPumpRun() = false │
min run time OK (300 s) │
│ │
[ STOPPING ] │
│ │
AUX lead ──► pump OFF ──► UVC post-delay ────────────────┘
Guards that bypass min-run time: FORCE_ON and FORCE_OFF — manual mode suspends timing guards.
Time → 0 5s 15s [pump runs…] Ts-30s Ts Ts+30s
│ │ │ │ │ │ │
UVC: ├──ON──────┼──────────┼────────────────┼────────┼─────────┼──OFF───┤
Pump: ON──────────────────────────────────OFF
AUX: ON───────────────OFF
◄─ pre ──►◄──────────────── RUNNING ──────────►◄─ lead ─►◄─ post─►
Ts = moment the stop sequence begins. pre = enableUVC(preDelayS, …). lead = enableAux(…, stopLeadS). post = enableUVC(…, postDelayS).
Every update() tick calls the priority engine. The first rule that matches wins:
| Priority | Condition | Result |
|---|---|---|
| P0 | Solar absorber > safety temp (default 50 °C) | Pump ON + valve OPEN — overrides FORCE_OFF |
| P1 | FORCE_OFF manual mode |
Pump OFF |
| P2 | FORCE_ON manual mode |
Pump ON |
| P3 | External request callback returns true |
Pump ON |
| P4 | Freeze: pool temp < threshold AND water present | Pump ON |
| P5a | Solar: absorber > pool + startDelta | Pump ON (hysteresis) |
| P5b | Catch-up: daily runtime < daily target (window OK) | Pump ON |
| P5c | Schedule callback returns true |
Pump ON |
| — | None of the above | Pump OFF |
PCF8574AT at I2C address 0x3C
│
├─ P0 ── Pump relay (always required)
├─ P1 ── UVC relay (optional — enableUVC())
├─ P2 ── AUX relay (optional — enableAux())
└─ P3 ── Solar valve relay (optional — enableSolar(…, useValve=true))
│
├─ P4 ── Extension relay (optional — setExtraOutput(4, on/off))
├─ P5 ── Extension relay (optional — setExtraOutput(5, on/off))
├─ P6 ── Extension relay (optional — setExtraOutput(6, on/off))
└─ P7 ── Extension relay (optional — setExtraOutput(7, on/off))
PCF HIGH = relay ON, LOW = relay OFF. begin() writes 0x00 immediately — all relays start OFF.
#include <Wire.h>
#include <APAPUMP.h>
ApaPump pump; // PCF at 0x3C — pump=P0, uvc=P1, aux=P2, valve=P3
void setup() {
Wire.begin(); // required for PCF mode — call before pump.begin()
pump.begin(); // all relays OFF, EEPROM loaded
}
void loop() {
pump.update(); // non-blocking — call every loop()
}// Active-high relay (most modules)
ApaPump pump(RELAY_DIRECT, 7); // pump on pin 7
// Active-low relay (some modules)
ApaPump pump(RELAY_DIRECT, 7);
pump.setActiveLow(); // call BEFORE pump.begin()
// Multiple relays, direct GPIO
ApaPump pump(RELAY_DIRECT, 7, 8, 9, 10); // pump=7, uvc=8, aux=9, valve=10#include <Wire.h>
#include <APAPUMP.h>
ApaPump pump;
bool scheduleActive() {
// return true when your RTC time falls inside a timer slot
return false; // replace with real logic
}
void onAlarm(PumpAlarm alarm) {
if (alarm == PUMP_ALARM_NONE) return; // alarm was cleared
Serial.print(F("Pump alarm: "));
switch (alarm) {
case PUMP_ALARM_OVERCURRENT: Serial.println(F("overcurrent")); break;
case PUMP_ALARM_LOW_PRESSURE: Serial.println(F("dry run")); break;
case PUMP_ALARM_HIGH_PRESSURE: Serial.println(F("high pressure")); break;
case PUMP_ALARM_NO_FLOW: Serial.println(F("no flow")); break;
default: break;
}
// pump continues running — call pump.acknowledgeAlarm() when investigated
}
void setup() {
Wire.begin();
pump.begin(scheduleActive); // schedule drives on/off
pump.enableUVC(5, 30); // UVC: 5 s pre, 30 s post
pump.enableAux(10, 30); // AUX: 10 s delay, 30 s lead
pump.setPumpAlarmCallback(onAlarm);
}
void loop() { pump.update(); }Force the pump on or off at any time. All timing guards and schedules are suspended:
pump.setManualMode(FORCE_ON); // force pump ON (e.g. vacuuming, winterising)
pump.setManualMode(FORCE_OFF); // force pump OFF (e.g. plumbing, service)
pump.setManualMode(AUTO); // return to automatic controlThe solar valve closes immediately when entering FORCE_ON — operator gets full system pressure.
Auto-return options — pick one or both:
// Timeout: returns to AUTO after 60 minutes
ApaPump pump(RELAY_PCF, 0x3C, 0, 1, 2, 3, 60); // 6th constructor parameter
pump.setManualTimeout(60); // or set at any time
// Midnight reset (requires setMidnightCallback())
pump.setManualAutoReset(true);Note: Solar safety (P0) still applies even in FORCE_OFF. If the absorber reaches the safety temperature, the pump runs to prevent heat damage regardless of manual mode.
Each follower is independent and optional. Wire the relay to the corresponding PCF bit (or GPIO pin), then call the enable method:
// UVC lamp: ON 5 s before pump, OFF 30 s after pump stops
pump.enableUVC(5, 30);
// AUX device (heat pump, ozone): ON 10 s after pump starts, OFF 30 s before pump stops
pump.enableAux(10, 30);
// Solar valve: open when solar logic drives the pump
// useValve=true enables the valve relay on P3 (or direct pin d)
pump.enableSolar(absorberTempCb, poolTempCb, /*useValve=*/true, ...);UVC pre-delay — when a pre-delay is configured, the pump enters STARTING state while UVC warms up. If the reason to start disappears during STARTING (e.g. schedule ends), the sequence is cancelled cleanly — UVC turns off and the pump never fires.
Solar logic becomes the sole on/off driver when enabled — the schedule callback is only used for the daily runtime target.
pump.enableSolar(
[]() { return adc.getSolarTemp(); }, // absorber temperature callback
[]() { return adc.getPoolTemp(); }, // pool temperature callback (optional)
true, // useValve — open valve when solar running
8.0f, // startDelta: start when absorber > pool + 8°C
3.0f, // stopDelta: stop when absorber < pool + 3°C
32.0f, // maxPoolTemp: pool cooling if pool > 32°C
2.0f, // coolDelta: cool when absorber < pool - 2°C
50.0f // safetyTemp: force pump ON if absorber > 50°C
);
// Optional: restrict solar heating to daytime hours
pump.setSolarDayNight(
[]() { return rtc.getEpoch(); }, // Unix epoch callback
7, // daytime starts at 07:00
20 // daytime ends at 20:00
);Absorber temp
│
│ START threshold = pool + startDelta
─────┼──────────────────────────────────────────────────────
│ ← pump ON pump ON →
│
─────┼──────────────────────────────────────────────────────
│ STOP threshold = pool + stopDelta
│
The gap between start and stop thresholds prevents rapid on/off cycling when temperature hovers near the boundary. Increase startDelta − stopDelta for wider hysteresis.
// Option A: fixed target (user sets it once)
pump.setDailyTarget(360); // run 6 hours per day
// Option B: use the APALCDGUI timer sum as the target
pump.begin(scheduleActive, nullptr,
[]() { return gui.getTimerTotalMinutes(); });
// Query progress
uint16_t ran = pump.getDailyRuntimeMinutes();
bool met = pump.isDailyTargetMet();When solar is enabled and the daily target is not met, catch-up runs until the target is reached:
// Optional: limit catch-up to daytime hours (requires setMidnightCallback)
pump.setCatchupWindow(8, 20); // catch-up only between 08:00 and 20:00All alarms are latching — the pump does not stop automatically (your alarmCb decides the action). Call acknowledgeAlarm() after investigation to clear.
| Alarm | Triggers when | Requires |
|---|---|---|
PUMP_ALARM_OVERCURRENT |
current > learned baseline × 1.5 | setCurrentCallback() |
PUMP_ALARM_LOW_PRESSURE |
pressure below 40% of EMA baseline (dry-run) | enablePressure() |
PUMP_ALARM_HIGH_PRESSURE |
pressure > maxPressure OR > EMA × (1+peakPct%) |
enablePressure() + setPressurePeakAlarm() |
PUMP_ALARM_NO_FLOW |
flow switch reports no flow after 30 s settle | setFlowCallback() |
Alarm callback pattern:
pump.setPumpAlarmCallback([](PumpAlarm alarm) {
if (alarm == PUMP_ALARM_NONE) {
// alarm was acknowledged — update LCD, clear indicator
gui.cancelActiveAlert();
return;
}
// alarm fired — notify operator
gui.postActiveAlert(F("Pump alarm!"), F("Check equipment"),
ALERT_CRITICAL, []() { pump.acknowledgeAlarm(); });
});The alarm callback is the right place to drive any physical indicator — buzzer, LED, relay. No extra library method needed:
pump.setPumpAlarmCallback([](PumpAlarm alarm) {
bool active = (alarm != PUMP_ALARM_NONE);
digitalWrite(5, active ? HIGH : LOW); // buzzer on pin 5
// LEDs on a PCF expander — drive via APASENSE:
// adc.setLed(4, active);
});Tip: if you use APALCDGUI, a future release will add
gui.setBuzzerPin(pin)to drive the buzzer automatically from the alert level (INFO / WARNING / CRITICAL) without any sketch code.
When enablePressure() is registered, APAPUMP builds a dual pressure baseline (EMA): one for normal running, one for when the solar valve is open (higher pressure expected due to absorber resistance). After 5 pump runs, if pressure stays near zero after 30 s, PUMP_ALARM_LOW_PRESSURE fires.
Before the EMA baseline builds (first 5 runs), an absolute minimum of 0.1 bar is used.
pump.enableFreezeProtection(
[]() { return adc.getPoolTemp(); }, // pool/pipe temperature
4.5f // threshold in °C (default)
);When pool temperature drops below the threshold, the pump cycles to prevent pipes from freezing: runs for APAPUMP_FREEZE_ON_SEC (default 5 min), rests for APAPUMP_FREEZE_OFF_SEC (default 10 min), and repeats until temperature rises. Both durations are overridable via build_flags. Dry-run interlock: if the pressure sensor is enabled, calibrated, and indicates no water in the pipes (pressure near zero), freeze protection is suppressed — forcing the pump without water would burn the motor.
APAPUMP, APADOSE, and APALCDGUI are independent libraries — your sketch is the bridge. No library knows about the others.
// In begin(): pass a lambda that reads the timer state from the GUI
pump.begin(
[]() {
// return true when current time falls inside any timer slot
uint16_t nowMin = rtcHour * 60 + rtcMinute;
for (uint8_t i = 0; i < APA_LCD_MAX_TIMERS; i++) {
if (gui.isTimerEnabled(i) &&
nowMin >= gui.getTimerStart(i) &&
nowMin < gui.getTimerEnd(i)) return true;
}
return false;
},
nullptr,
[]() { return gui.getTimerTotalMinutes(); } // daily target from timer sum
);// After a shock dose, run the pump for 4 hours to circulate the chlorine.
// Uses the externalRequestCb — no new API needed.
static uint32_t postShockUntil = 0;
pump.begin(scheduleCb,
[]() {
// Shock is running: extend the post-shock window
if (dose1.isShockActive()) {
postShockUntil = millis() + 4UL * 3600UL * 1000UL;
return true;
}
// Pump on until post-shock window expires
return (millis() < postShockUntil);
}
);// Show [M] in the LCD corner whenever the pump is in manual mode
pump.setStatusCallback([](const __FlashStringHelper* msg) {
if (pump.getManualMode() != AUTO) gui.setStatusIndicator('M');
else gui.clearStatusIndicator();
// Also forward the status text to a scrolling message area
Serial.println(msg);
});// Order: adc.begin() BEFORE pump.begin() — pressure auto-zeros on first pump stop.
// pressureCb returns -1.0f while APASENSE is uncalibrated — APAPUMP skips
// all pressure logic until a valid reading arrives.
adc.begin(); // zero-cal requires pump off — call first
pump.begin();
pump.enablePressure(
[]() { return adc.getPressure(); }, // -1.0f until calibrated
4.0f // absolute max pressure (bar)
);
pump.setCurrentCallback([]() { return adc.getCurrent(); });
// Bridge: tell APASENSE when pump state changes so it can re-zero on pump stop
pump.setPumpStateCallback([](bool on) { adc.onPumpState(on); });| Sketch | Level | Description |
|---|---|---|
examples/01_minimal/ |
Basic | PCF or GPIO, manual override via Serial, all three constructor options |
examples/02_scheduler/ |
Intermediate | APALCDGUI timer schedule, UVC + AUX followers, alarm → active alert bridge |
examples/03_solar_freeze/ |
Advanced | Solar heater + solar valve, freeze protection, pressure safety, APADOSE post-shock bridge |
Compiled with the 01_minimal example. Zero errors, zero library warnings on all platforms.
| Platform | Board | RAM used | RAM total | Flash used | Flash total |
|---|---|---|---|---|---|
| Arduino Mega 2560 | ATmega2560 | 564 B | 8 192 B (6.9%) | 11 860 B | 253 952 B (4.7%) |
| Arduino Uno | ATmega328P | 564 B | 2 048 B (27.5%) | 11 094 B | 32 256 B (34.4%) |
| ESP32 DevKit | ESP32 | 22 024 B | 327 680 B (6.7%) | 290 493 B | 1 310 720 B (22.2%) |
| ESP8266 D1 Mini | ESP8266 | 28 852 B | 81 920 B (35.2%) | 274 147 B | 1 044 464 B (26.2%) |
| STM32 Bluepill | STM32F103C8 | 2 628 B | 20 480 B (12.8%) | 25 984 B | 65 536 B (39.6%) |
The Uno row uses 27.5% RAM — that is the library with all Phase 2 features registered in the example. A minimal sketch (no solar, no pressure, no freeze) sits below 20%. ESP32 and ESP8266 totals include the full Arduino framework regardless of use.
APAPUMP reserves 12 bytes starting at APAPUMP_EEPROM_ADDR (default 520).
| Address | Bytes | Field | Saved when |
|---|---|---|---|
| 520 | 2 | Magic 0xA55A |
— validity marker |
| 522 | 1 | Config version | — mismatch resets all fields to defaults |
| 523 | 2 | Daily target (minutes) | setDailyTarget() |
| 525 | 2 | Yesterday's runtime (minutes) | Midnight rollover (once per day) |
| 527 | 2 | Minimum run time (seconds) | setMinRunTime() |
| 529 | 2 | Clean pressure × 100 (bar; 0 = not learned) | learnCleanPressure() / setCleanPressure() |
| 531 | 1 | Checksum (byte sum of bytes 520–530) | — corruption guard |
_saveEEPROM() writes the full 12-byte struct, but a physical write only occurs when a byte has actually changed:
- AVR (Uno/Mega):
EEPROM.put()callsEEPROM.update()per byte — reads first, writes only if value differs. - ESP32/ESP8266:
EEPROM.put()updates a RAM buffer;EEPROM.commit()compares the buffer to flash before writing — no flash write if content unchanged. - STM32: EEPROM emulation with compare-before-write.
Practical write frequency (worst case on a running system):
| Event | Max frequency | Cycles used at 100 k limit |
|---|---|---|
| Midnight rollover | 1 per day | 100 k days ≈ 273 years |
learnCleanPressure() |
Operator action | Negligible |
setMinRunTime() from setup() |
0 physical writes if value unchanged | None |
| First boot / corruption recovery | Once | 1 cycle |
Corruption recovery: the checksum is verified on every begin(). If power fails mid-write and data is corrupted, the mismatch is detected on the next boot, factory defaults are loaded, and a clean struct is written.
// Define before #include if the default conflicts with another library in your project:
#define APAPUMP_EEPROM_ADDR 532
#include <APAPUMP.h>All ranges across the APA library suite — free blocks shown explicitly:
| Range | Bytes | Status | Owner |
|---|---|---|---|
| 0–127 | 128 | free | — |
| 128–177 | 50 | used | APAPHX2_ADS1115 (sensor calibration) |
| 178–188 | 11 | free | — |
| 189–191 | 3 | used | APADOSE global (pool volume, dead-band) |
| 192–279 | 88 | used | APADOSE per-pump config (22 bytes × up to 4 instances) |
| 280–499 | 220 | free | — |
| 500–501 | 2 | used | APALCDGUI brightness |
| 502–508 | 7 | used | APALCDGUI timer slots (default 3 slots) |
| 509–519 | 11 | free | — gap before APAPUMP ¹ |
| 520–531 | 12 | used | APAPUMP |
| 532– | — | free | — |
¹ When
APA_LCD_MAX_TIMERS=6the timer block extends to 514, leaving a 5-byte gap (515–519) before APAPUMP. This gap is intentional — do not place anything in 515–519 to keep the gap safe regardless of timer configuration.
Dual license — see LICENSE file for full terms.
| Use | License |
|---|---|
| Personal, private, educational, hobby | Free — no charge, no paperwork |
| Commercial (products, services, OEM) | Separate written license required |
Commercial use includes selling or distributing hardware with this software, providing paid pool automation services, or integrating it into any revenue-generating product or system.