NeoPool / Vistapool Control System — MODBUS Register Description

Merged reference combining two upstream documents:

Where both sources document the same address, the 2015 text is canonical and the v10.23 wording is referenced via callouts. Registers introduced in v10.23 are marked Documented in 2023 v10.23 (Hayward / Vistapool); not present in 2015 NeoPool spec.

Two addresses (0x0403 and 0x0430) are documented under different names and meanings in the two sources — those entries carry an explicit Note (v10.23 firmware) callout pointing at the alternate definition.


Sources

Year Maker Filename Notes
2015 Sugar Valley / NeoPool docs/modbus-registers-v2015.md Canonical text for shared registers
2023 Hayward / Vistapool v10.23 docs/modbus-registers-v2023.md New registers; conflict callouts at 0x0403 / 0x0430

Table of Contents

  1. Introduction
  2. Register Description

1 Introduction

The NeoPool / Vistapool Control System is equipped with RS485 communication ports using a MODBUS protocol that allows a remote controller to adjust the different working parameters of the device. The 2015 spec mentions two such ports; the 2023 v10.23 spec lists three.

The first port, labelled on the board as "DISPLAY", is usually connected to the Screen Controller, which is itself a MODBUS master. The other port, labelled as "RF/WIFI", is available for external communications.

A semaphore system has been implemented between all ports in order to manage register change requests happening simultaneously in both ports. However, the remote masters can always read any register concurrently.

The slave has the MODBUS address 1 as default communication address, but it can be changed with a reserved procedure (see MBF_NODE_ADDR).

Communication parameters for the RS485 asynchronous serial port:

Parameter Value
Baud rate 19200 bauds
Parity None
Stop bits 1

Warning: The alteration of registers other than the ones described in this document could lead to a bad operation of the system, and in some cases, to an unrecoverable failure requiring technical assistance.


2 Register Description

The register set is divided into 7 different pages:

Starting Address Name Description
0x0000 MODBUS Manages general configuration of the box. This page is reserved for internal purposes.
0x0100 MEASURE Contains the different measurement information including hydrolysis current, pH level, redox level, etc.
0x0200 GLOBAL Contains global information, such as the amount of time that each power unit has been working.
0x0300 FACTORY Contains factory data such as calibration parameters for the different power units.
0x0400 INSTALLER Contains a set of configuration registers related to the box installation, such as the relays used for each function, the amount of time that each pump must operate, etc.
0x0500 USER Contains user configuration registers, such as the production level for the ionization and the hydrolysis, or the set points for the pH, redox, or chlorine regulation loops.
0x0600 MISC Contains the configuration parameters for the screen controllers (language, colours, sound, etc.).

Any modifications done over the registers should be made persistent by requesting an EEPROM storage. See MBF_SAVE_TO_EEPROM for more information.


2.1 Modbus Page (MODBUS)

Register 0x0000 - MBF_NODE_ADDR

Documented in 2023 v10.23 (Hayward / Vistapool); not present in 2015 NeoPool spec.

This register contains the current MODBUS slave address. Writing to this register changes the MODBUS address of the node.

The value of this register must be in the range of 1 to 240, both inclusive. Address 0 is reserved for sending broadcast messages to all devices.

When a write to this register occurs, the system must complete the write transaction by sending the response message, and only after that perform the change of the MODBUS address.


2.2 Measures Page (MEASURE)

Register 0x0100 - MBF_ION_CURRENT

Current measured in the ionization system. The value is obtained from the microcontroller ADC and corrected using the calibration data:

  • MBF_PAR_ION_NOM: Maximum ionization current
  • MBF_PAR_ION_CAL0: ADC value measured at idle state
  • MBF_PAR_ION_CAL1: ADC value measured at maximum ionization current

Formula: MBF_ION_CURRENT = (adcValue - MBF_PAR_ION_CAL0) / (MBF_PAR_ION_CAL1 - MBF_PAR_ION_CAL0) * MBF_PAR_ION_NOM


Register 0x0101 - MBF_HIDRO_CURRENT

Current working level measured in the hydrolysis/electrolysis system.

Formula: MBF_HIDRO_CURRENT = (hidroAdcValue - MBF_PAR_HIDRO_CAL0) / (MBF_PAR_HIDRO_CAL1 - MBF_PAR_HIDRO_CAL0) * MBF_PAR_HIDRO_NOM


Register 0x0102 - MBF_MEASURE_PH

pH level measured in hundredths. A value of 700 means pH 7.00.

This register is only valid if the pH module is enabled. Check MBF_PH_STATUS for the module status.


Register 0x0103 - MBF_MEASURE_RX

Redox/ORP level measured in hundredths of ppm. A value of 100 means 1.00 ppm.

This register is only valid if the Redox module is enabled. Check MBF_RX_STATUS.


Register 0x0104 - MBF_MEASURE_CL

Chlorine concentration level measured in hundredths of ppm. A value of 100 means 1.00 ppm.

This register is only valid if the Chlorine module is enabled. Check MBF_CL_STATUS.


Register 0x0105 - MBF_MEASURE_CONDUCTIVITY

Conductivity level measured in the water. Only valid if the conductivity module is enabled. Check MBF_CD_STATUS.


Register 0x0106 - MBF_MEASURE_TEMPERATURE

Temperature measured by the water temperature sensor, in tenths of degrees Celsius. A value of 200 means 20.0 °C.


Register 0x0107 - MBF_PH_STATUS

Status of the pH control module. Bitmask:

Bits Mask Description
0-3 0x000F pH alarm (see alarm value tables below)
7 0x0080 Regulation out of range (value on the wrong side of setpoint; not exposed as entity — too sensitive for practical use)
10 0x0400 pH control module controlled by flow detection (if enabled via MBF_PAR_HIDRO_ION_CAUDAL)
11 0x0800 Low pH pump relay on (pump activated)
12 0x1000 High pH pump relay on (pump activated)
13 0x2000 pH control module active and controlling pumps
14 0x4000 pH measurement module active and taking measurements
15 0x8000 pH measurement module detected

pH alarm values for acid and base regulation:

Value Description
0 No alarm
1 pH too high: pH value exceeds PH1 setpoint by 0.8 units
2 pH too low: pH value is below PH2 setpoint by 0.8 units
3 pH pump (acid or base) exceeded the maximum working time set in MBF_PAR_RELAY_PH_MAX_TIME and has been stopped
4 pH value is above PH1 setpoint
5 pH value is below PH2 setpoint
6 Acid or base tank empty (float switch tripped)

pH alarm values for acid-only regulation:

Value Description
0 No alarm
1 pH too high: pH value exceeds PH1 setpoint by 0.8 units
2 pH too low: pH value is below PH1 setpoint by 0.8 units
3 pH pump exceeded maximum working time and has been stopped
4 pH value is above PH1 setpoint + 0.1
5 pH value is below PH1 setpoint - 0.3
6 Acid tank empty (float switch tripped)

pH alarm values for base-only regulation:

Value Description
0 No alarm
1 pH too high: pH value exceeds PH2 setpoint by 0.8 units
2 pH too low: pH value is below PH2 setpoint by 0.8 units
3 pH pump exceeded maximum working time and has been stopped
4 pH value is above PH2 setpoint + 0.1
5 pH value is below PH2 setpoint - 0.3
6 Base tank empty (float switch tripped)

Register 0x0108 - MBF_RX_STATUS

Status of the Redox/ORP control module. Bitmask:

Bits Mask Description
7 0x0080 Regulation out of range (Redox below setpoint; not exposed as entity — too sensitive for practical use)
12 0x1000 Redox pump relay on (pump activated)
13 0x2000 Redox control module active and controlling pump
14 0x4000 Redox measurement module active and taking measurements
15 0x8000 Redox measurement module detected in the system

Register 0x0109 - MBF_CL_STATUS

Status of the chlorine control module. Bitmask:

Bits Mask Description
3 0x0008 Chlorine probe flow sensor. Integrated in the probe itself; detects if water is passing through the chlorine measurement probe. If 0, the chlorine measurement is not valid.
7 0x0080 Regulation out of range (value on the wrong side of setpoint; not exposed as entity — too sensitive for practical use)
12 0x1000 Chlorine pump relay on (pump activated)
13 0x2000 Chlorine control module active and controlling pump
14 0x4000 Chlorine measurement module active and taking measurements (display bar should be shown)
15 0x8000 Chlorine measurement module detected in the system

Register 0x010A - MBF_CD_STATUS

Status of the conductivity control module. Bitmask:

Bits Mask Description
7 0x0080 Regulation out of range (value on the wrong side of setpoint; not exposed as entity — too sensitive for practical use)
12 0x1000 Conductivity pump relay on (pump activated)
13 0x2000 Conductivity control module active and controlling pump
14 0x4000 Conductivity measurement module active and taking measurements (display bar should be shown)
15 0x8000 Conductivity measurement module detected in the system

Register 0x010C - MBF_ION_STATUS

Status of the ionization control module. Bitmask:

Bit Mask Description
0 0x0001 On Target - the system has reached the configured setpoint
1 0x0002 Low - the ionization cannot reach the configured setpoint
2 0x0004 Elec - reserved
3 0x0008 Pr off - the programmed ionization time has been exceeded
12 0x1000 Ion Pol off - ionization in dead time
13 0x2000 Ion Pol 1 - ionization working in polarization 1
14 0x4000 Ion Pol 2 - ionization working in polarization 2

Register 0x010D - MBF_HIDRO_STATUS

Status of the hydrolysis/electrolysis control module. Bitmask:

Bit Mask Description
0 0x0001 On Target - the system has reached the configured setpoint
1 0x0002 Low - the hydrolysis cannot reach the configured setpoint
2 0x0004 Elec - reserved
3 0x0008 Flow - cell flow indicator (FL1)
4 0x0010 Cover - cover input active
5 0x0020 Active - hydrolysis module active (hydroEnable)
6 0x0040 Control - hydrolysis working in regulation mode (hydroControlEnable)
7 0x0080 Redox enable - hydrolysis activation by the Redox module (rx_hen)
8 0x0100 Hidro shock enabled - chlorine shock mode active
9 0x0200 FL2 - chlorine probe flow indicator, if present
10 0x0400 Cl enable - hydrolysis activation by the chlorine module (cl_hen)
11 0x0800 Not used
12 0x1000 Ion Pol off - ionization in dead time
13 0x2000 Ion Pol 1 - ionization working in polarization 1
14 0x4000 Ion Pol 2 - ionization working in polarization 2
15 0x8000 Not used

Register 0x010E - MBF_RELAY_STATE

State of all configurable relays. Bitmask:

Bit Mask Description
0 0x0001 Relay 1 state (1=on, 0=off) - normally assigned to pH
1 0x0002 Relay 2 state (1=on, 0=off) - normally assigned to filtration
2 0x0004 Relay 3 state (1=on, 0=off) - normally assigned to lighting
3 0x0008 Relay 4 state
4 0x0010 Relay 5 state
5 0x0020 Relay 6 state
6 0x0040 Relay 7 state

Register 0x010F - MBF_HIDRO_SWITCH_VALUE

Hydrolysis PWM duty cycle (0-65535). An internal value indicating the voltage being applied by the system to the hydrolysis cell to achieve the desired production current.


Register 0x0110 - MBF_NOTIFICATION

Bitmask indicating which register page has changed since the last time it was read. This enables a MODBUS master to refresh its cached register values in an optimized way, only re-reading pages that have changed rather than polling all registers periodically.

It is the responsibility of the MODBUS master to clear this register to 0 once the modified page registers have been read.

Bit Mask Description
0 0x0001 MBMSK_NOTIF_MODBUS_CHANGED
1 0x0002 MBMSK_NOTIF_GLOBAL_CHANGED
2 0x0004 MBMSK_NOTIF_FACTORY_CHANGED
3 0x0008 MBMSK_NOTIF_INSTALLER_CHANGED
4 0x0010 MBMSK_NOTIF_USER_CHANGED
5 0x0020 MBMSK_NOTIF_MISC_CHANGED

Register 0x0111 - MBF_HIDRO_VOLTAGE

Voltage applied to the hydrolysis cell. Together with MBF_HIDRO_CURRENT (0x0101), this register allows extrapolation of the water salinity.



2.3 Global Page (GLOBAL)

Registers 0x0206-0x0207 - MBF_PAR_HIDRO_WORK_TIME_LOW and MBF_PAR_HIDRO_WORK_TIME_HIGH

Documented in 2023 v10.23 (Hayward / Vistapool); not present in 2015 NeoPool spec.

This set of two registers contains the number of seconds that the chlorination cell has been working since the device was manufactured. The two registers must be read consecutively to build a 32-bit unsigned integer with the time.

This counter must not be erased as it is used to estimate the lifetime of the device.


Registers 0x0208-0x0209 - MBF_PAR_PARTIAL_HIDRO_WORK_TIME_LOW and MBF_PAR_PARTIAL_HIDRO_WORK_TIME_HIGH

Documented in 2023 v10.23 (Hayward / Vistapool); not present in 2015 NeoPool spec.

This set of two registers contains the number of seconds that the chlorination cell has been working since the counter was reset (partial counter). The two registers must be read consecutively to build a 32-bit unsigned integer with the time.

This counter is reset each time the cell is changed by the installer and it is used to estimate the total working time of a cell.


Register 0x02F0 - MBF_SAVE_TO_EEPROM

Writing the value 1 to this register immediately starts an EEPROM storage operation. During the EEPROM storage procedure, the system may be unresponsive to MODBUS requests. The operation will always last less than 1 second.

EEPROM write operations occur automatically every 10 minutes. However, after modifying a MODBUS configuration register it is recommended to force a write operation, as this is the only safe way to preserve the information if the box is switched off before the periodic EEPROM write automatically occurs.

Warning: The number of EEPROM write operations is guaranteed to be 100,000 cycles. Once this number is exceeded, safe storage of information cannot be guaranteed.


Register 0x02F1 - MBF_CLEAR_EEPROM

Documented in 2023 v10.23 (Hayward / Vistapool); not present in 2015 NeoPool spec.

A write operation to this register (with any value) restores the register memory to its factory default state immediately. This operation does not store the values into non-volatile EEPROM memory. To store the contents of the factory default state, a MBF_SAVE_TO_EEPROM operation has to be executed.


Register 0x02F2 - MBF_RESET_USER_COUNTERS

Documented in 2023 v10.23 (Hayward / Vistapool); not present in 2015 NeoPool spec.

A write operation to this register (with any value) resets the user time counters:

  • MBF_PAR_PARTIAL_HIDRO_WORK_TIME
  • MBF_PAR_PARTIAL_ION_WORK_TIME
  • MBF_PAR_PARTIAL_UV_WORK_TIME

These counters are associated with the user-level access.

This operation does not store the values into non-volatile EEPROM memory. To store the contents of the factory default state, a MBF_SAVE_TO_EEPROM operation has to be executed.


Register 0x02F4 - MBF_STOP_ALL_MODULES

Documented in 2023 v10.23 (Hayward / Vistapool); not present in 2015 NeoPool spec.

A write operation to this register (with any value) stops the operation of all modules. The following operational functions are affected:

  • Hydrolysis / Chlorination
  • Ionization
  • pH, ORP, Conductivity and chlorine control
  • Ultraviolet water depuration
  • Filtration pump control
  • All auxiliary relays

The operation of all those functions can be relaunched by means of the MBF_RESTART_MODULES register.


Register 0x02F5 - MBF_RESTART_MODULES

Documented in 2023 v10.23 (Hayward / Vistapool); not present in 2015 NeoPool spec.

A write operation to this register (with any value) restarts the operation of all function modules of the device. The following operational functions are affected:

  • Hydrolysis / Chlorination
  • Ionization
  • pH, ORP, Conductivity and chlorine control
  • Ultraviolet water depuration
  • Filtration pump control
  • All auxiliary relays

It is recommended to relaunch all modules if a parameter change has taken place, like filtration scheduler programming, filtration mode, etc.


2.4 Factory Page (FACTORY)

Warning: The factory registers marked as "DO NOT MODIFY" must not be changed. Uncontrolled modification of these registers could lead to bad operation of the system, and in some cases to an unrecoverable failure requiring technical assistance.


Register 0x0300 - MBF_PAR_VERSION

PowerBox software version. Not used.


Register 0x0301 - MBF_PAR_MODEL

Equipment model options bitmask. DO NOT MODIFY.

Bit Mask Name Description
0 0x0001 MBMSK_MODEL_ION Device includes copper-silver ionization control
1 0x0002 MBMSK_MODEL_HIDRO Device includes hydrolysis or electrolysis
2 0x0004 MBMSK_MODEL_UV Device includes UV lamp disinfection control
3 0x0008 MBMSK_MODEL_SALINITY Device includes salinity measurement (Fanless devices only)

Register 0x0302 - MBF_PAR_SERNUM

Equipment serial number. Not used.


Register 0x0303 - MBF_PAR_ION_NOM

Maximum ionization production level. DO NOT MODIFY.


Register 0x0306-0x0307 - MBF_PAR_HIDRO_NOM

Maximum hydrolysis/electrolysis production level. If the hydrolysis module operates in percent mode, this value is 100. If operating in g/h mode, this value contains the maximum production in g/h units. DO NOT MODIFY.


Register 0x030A - MBF_PAR_SAL_AMPS

Current setpoint (in regulation) at which voltage is measured for salinity calculation.


Register 0x030B - MBF_PAR_SAL_CELLK

Cell constant: the relationship between the measured resistance in the measurement process and its equivalence in g/l (grams per liter).

Salinity formula: $$\text{Salinity}{23°C} = \frac{R{CELL}}{K_{CELL}} \cdot \frac{1}{1 + T_{COMP} \cdot (T - 23°C)}$$


Register 0x030C - MBF_PAR_SAL_TCOMP

Temperature deviation coefficient of conductivity for salinity calculation.


Register 0x0322 - MBF_PAR_HIDRO_MAX_VOLTAGE (Fanless devices only)

Maximum voltage in tenths of a volt that can be reached by the hydrolysis current regulation. Default: 80 (= 8.0 V maximum cell operating voltage).

To make changes persistent, execute the EEPROM storage procedure described in MBF_SAVE_TO_EEPROM.


Register 0x0323 - MBF_PAR_HIDRO_FLOW_SIGNAL (Fanless devices only)

Flow detection signal configuration for hydrolysis operation:

Value Name Description
0 MBV_PAR_HIDRO_FLOW_SIGNAL_STD Standard detection based on conduction between an auxiliary electrode and either cell electrode
1 MBV_PAR_HIDRO_FLOW_SIGNAL_ALWAYS_ON Always connected - forces hydrolysis current generation even without flow detected
2 MBV_PAR_HIDRO_FLOW_SIGNAL_PADDLE Detection based on paddle switch connected to FL1 input
3 MBV_PAR_HIDRO_FLOW_SIGNAL_PADDLE_AND_STD Both paddle switch (FL1) AND standard detection; flow is detected when BOTH detect flow; hydrolysis stops if either opens
4 MBV_PAR_HIDRO_FLOW_SIGNAL_PADDLE_OR_STD Paddle switch (FL1) OR standard detection; flow is detected when EITHER detects flow; hydrolysis stops only if BOTH detect no flow

Default: 0 (standard detection).

To make changes persistent, execute the EEPROM storage procedure described in MBF_SAVE_TO_EEPROM.


Register 0x0324 - MBF_PAR_HIDRO_MAX_PWM_STEP_UP (Fanless devices only)

PWM ramp-up rate in pulses per work cycle for hydrolysis. Controls the rate at which power delivered to the cell increases, enabling a gradual power ramp-up so as not to saturate the switching power supply. Default: 150.

To make changes persistent, execute the EEPROM storage procedure described in MBF_SAVE_TO_EEPROM.


Register 0x0325 - MBF_PAR_HIDRO_MAX_PWM_STEP_DOWN (Fanless devices only)

PWM ramp-down rate in pulses per work cycle for hydrolysis. Controls the rate at which power delivered to the cell decreases gradually, preventing the switching power supply from disconnecting due to lack of load. The ramp-down rate must match the type of cell used, as the cell stores charge after the current stimulus ceases. Default: 20.

To make changes persistent, execute the EEPROM storage procedure described in MBF_SAVE_TO_EEPROM.



2.5 Installer Page (INSTALLER)

Register 0x0400 - MBF_PAR_ION_POL0

Time in minutes that the system must remain working in positive polarization during copper-silver ionization.

To make changes persistent, execute the EEPROM storage procedure described in MBF_SAVE_TO_EEPROM.


Register 0x0401 - MBF_PAR_ION_POL1

Time in minutes that the system must remain working in negative polarization during copper-silver ionization.

To make changes persistent, execute the EEPROM storage procedure described in MBF_SAVE_TO_EEPROM.


Register 0x0402 - MBF_PAR_ION_POL2

Time in minutes that the system must remain in dead time (no power delivery) during copper-silver ionization.

To make changes persistent, execute the EEPROM storage procedure described in MBF_SAVE_TO_EEPROM.


Register 0x0403 - MBF_PAR_HIDRO_ION_CAUDAL

Bitmask controlling external control of ionization, hydrolysis, and pumps. Active bits enable the corresponding behavior:

Bit Mask Name Description
0 0x0001 FL1_CTRL If FL1 signal is inactive, disable all system elements
1 0x0002 FL2_CTRL If FL2 signal is inactive, disable all system elements
2 0x0004 FULL_CL_HIDRO_CTRL If a Cl module is installed and its flow sensor is inactive, disable all system elements
3 0x0008 SLAVE If slave input is inactive, disable all system elements
4 0x0010 PADDLE_SWITCH Enable paddle switch
5 0x0020 PADDLE_SWITCH_INV Enable inverted paddle switch
7 0x0080 INVERSION Determines whether "active" means open or closed for input signals; allows inverting behavior (e.g., a paddle that closes when there is no flow)

To make changes persistent, execute the EEPROM storage procedure described in MBF_SAVE_TO_EEPROM.

Note (v10.23 firmware): the same address 0x0403 is documented in the 2023 Hayward Vistapool spec under a different name — MBF_PAR_EXT_CTRL — but with the same bit-field semantics (FL1_CTRL / FL2_CTRL / FULL_CL_HIDRO_CTRL / SLAVE / PADDLE_SWITCH / PADDLE_SWITCH_INV / INVERSION). Only the symbolic name differs; the actual register layout and meaning match the 2015 MBF_PAR_HIDRO_ION_CAUDAL description above. See docs/modbus-registers-v2023.md for the v10.23 wording.


Register 0x0404 - MBF_PAR_HIDRO_MODE

External hydrolysis control mode from measurement modules:

Value Description
0 No control
1 Standard control (on/off)
2 With timed pump

Register 0x0405 - MBF_PAR_HIDRO_POL0

Time in minutes for hydrolysis/electrolysis positive polarization.

To make changes persistent, execute the EEPROM storage procedure described in MBF_SAVE_TO_EEPROM.


Register 0x0406 - MBF_PAR_HIDRO_POL1

Time in minutes for hydrolysis/electrolysis negative polarization.

To make changes persistent, execute the EEPROM storage procedure described in MBF_SAVE_TO_EEPROM.


Register 0x0407 - MBF_PAR_HIDRO_POL2

Time in minutes for hydrolysis/electrolysis dead time (no power delivery).

To make changes persistent, execute the EEPROM storage procedure described in MBF_SAVE_TO_EEPROM.


Registers 0x0408-0x0409 - MBF_PAR_TIME_LOW and MBF_PAR_TIME_HIGH

Two registers forming a 32-bit time counter. This counter stores the system time as seconds elapsed since January 1, 1970 (Unix Epoch).

  • MBF_PAR_TIME_LOW (0x0408): Low 16 bits
  • MBF_PAR_TIME_HIGH (0x0409): High 16 bits

See also MBF_ACTION_COPY_TO_RTC (0x04F0) for writing this time to the hardware RTC.


Register 0x040A - MBF_PAR_PH_ACID_RELAY_GPIO

Relay number assigned to the acid pump function (pH modules only).


Register 0x040B - MBF_PAR_PH_BASE_RELAY_GPIO

Relay number assigned to the base pump function (pH modules only).


Register 0x040C - MBF_PAR_RX_RELAY_GPIO

Relay number assigned to the Redox regulation function. If the value is 0, no relay is assigned and therefore there is no pump function.

To check whether this relay is active:

  • Method 1: Check the MBMSK_RX_STATUS_RELAY bit in MBF_RX_STATUS
  • Method 2: Calculate the bit assigned to the relay in MBF_RELAY_STATE

Register 0x040D - MBF_PAR_CL_RELAY_GPIO

Relay number assigned to the chlorine pump function (free chlorine measurement modules only).


Register 0x040E - MBF_PAR_CD_RELAY_GPIO

Relay number assigned to the conductivity pump function (brine) (conductivity measurement modules only).


Register 0x040F - MBF_PAR_TEMPERATURE_ACTIVE

Indicates whether the device has temperature measurement: 1 = yes, 0 = no.


Register 0x0410 - MBF_PAR_LIGHTING_GPIO

Relay number assigned to the lighting function. 0 = inactive.


Register 0x0411 - MBF_PAR_FILT_MODE

Filtration mode:

Value Name Description
0 MANUAL Always available. Allows filtration (and all dependent systems) to be switched on and off manually.
1 AUTO Always available. Filtration is switched on and off according to the configuration of timers TIMER1, TIMER2, and TIMER3.
2 HEATING Similar to AUTO mode, but includes temperature configuration for the heating function. Requires MBF_PAR_HEATING_MODE = 1 and an assigned heating relay.
3 SMART Adjusts pump working times based on water temperature. Requires MBF_PAR_TEMPERATURE_ACTIVE = 1.
4 INTELLIGENT Most complex mode - combines temperature and heating. Requires both MBF_PAR_TEMPERATURE_ACTIVE = 1 and MBF_PAR_HEATING_MODE = 1.
13 BACKWASH Started when the backwash operation is activated.
14 CHLORINATION SHOCK Started when the chlorination shock operation is activated.

Mode 0: MANUAL

This mode allows the filtration to be switched on and off manually. No timers or additional functions are involved. The state is controlled via MBF_PAR_FILT_MANUAL_STATE.

Mode 1: AUTO (timed)

Filtration is switched on according to timers. The timers allow setting start and end times for filtration. Timers always operate on a daily basis.

Mode 2: HEATING (timed with optional climate control)

Works like AUTO mode but also includes a relay that is activated or deactivated based on water temperature. The setpoint temperature is configured in this mode, and the system uses a 1-degree hysteresis.

Additionally, there is an optional "climate control" (shown on screen as "CLIMA" on/off). This option keeps the filtration running after its scheduled period if the temperature is below the setpoint. When the setpoint is reached, filtration stops and does not restart until the next scheduled period.

Example of hysteresis: if the setpoint is 23 °C, the system activates when temperature drops below 22 °C and stops when it exceeds 23 °C.

Note: This mode is only visible when the temperature sensor option is active and heating is enabled.

Mode 3: SMART

Based on the AUTO/timed mode, but adjusts filtration times based on temperature. Two temperature parameters are provided: the maximum temperature (at which filtration times follow the configured timers) and the minimum temperature (at which filtration is reduced to 5 minutes, the minimum working time). Filtration times scale linearly between these two temperatures.

Additionally there is an optional anti-freeze mode, which keeps filtration on if the system temperature is below 2 °C.

Note: This mode is only visible when the temperature sensor option is active.

Mode 4: INTELLIGENT

The most complex filtration mode. It involves both temperature and heating.

The user has two working parameters:

  • Desired temperature
  • Minimum filtration time (minimum 2 hours, maximum 24 hours) = Tfilt

Operation:

  • The system starts filtration every 2 hours.
  • The minimum filtration time is divided into 12 segments (Tfon = Tfilt/12).
  • A variable Tbonus = Tfilt - 2 hours is created.
  • After 10 minutes, Tbonus starts counting down. When Tbonus is exhausted, filtration stops.
  • After Tfon, the temperature is measured (the first 10 minutes ensure sufficient water flow). If the temperature is at or above the setpoint, filtration stops.
  • If the temperature is below the setpoint, filtration continues and the time is deducted from Tbonus.
  • Filtration runs a minimum of 10 minutes every 2 hours to check temperature. So the minimum filtration in intelligent mode is 2 hours per day (10 min × 12 times).

Example: with 10 hours minimum filtration time: 10h × 60min / 12 = 50 minutes per 2-hour interval. Of those 50 minutes, 10 are mandatory and 40 are used when heating is needed.

Note: This mode is only visible when the temperature sensor option is active.


Register 0x0412 - MBF_PAR_FILT_GPIO

Relay selected for the filtration function (default: relay 2). When this value is 0, no relay is assigned and the equipment does not control filtration; the filtration option will not appear in the user menu.


Register 0x0413 - MBF_PAR_FILT_MANUAL_STATE

Filtration state in manual mode: 1 = on, 0 = off.


Register 0x0414 - MBF_PAR_HEATING_MODE

Heating mode: 0 = the device has no heating, 1 = the device has heating.


Register 0x0415 - MBF_PAR_HEATING_GPIO

Relay selected for the heating function (default: relay 7). When this value is 0, no relay is assigned and the heating-related filtration modes will not be shown.


Register 0x0416 - MBF_PAR_HEATING_TEMP

Heating setpoint temperature.


Register 0x0417 - MBF_PAR_CLIMA_ONOFF

Climate mode activation: 0 = inactive, 1 = active.


Register 0x0418 - MBF_PAR_SMART_TEMP_HIGH

Upper temperature threshold for Smart filtration mode.


Register 0x0419 - MBF_PAR_SMART_TEMP_LOW

Lower temperature threshold for Smart filtration mode.


Register 0x041A - MBF_PAR_SMART_ANTI_FREEZE

Anti-freeze mode: 1 = enabled, 0 = disabled. Only available in Smart filtration mode.


Register 0x041B - MBF_PAR_SMART_INTERVAL_REDUCTION

Read-only. Reports what percentage (0-100%) is being applied to the nominal filtration time. A value of 100% means the full programmed filtration time is active.


Register 0x041C - MBF_PAR_INTELLIGENT_TEMP

Temperature setpoint for Intelligent filtration mode.


Register 0x041D - MBF_PAR_INTELLIGENT_FILT_MIN_TIME

Minimum filtration time in minutes for Intelligent mode.


Register 0x041E - MBF_PAR_INTELLIGENT_BONUS_TIME

Bonus time for the current set of intervals in Intelligent mode.


Register 0x041F - MBF_PAR_INTELLIGENT_TT_NEXT_INTERVAL

Time remaining until the next filtration interval in Intelligent mode. When it reaches 0, a new interval starts and the counter is reloaded with the interval period (2 × 3600 seconds).


Register 0x0420 - MBF_PAR_INTELLIGENT_INTERVALS

Number of started intervals in Intelligent mode. When it reaches 12, it resets to 0 and the bonus time is reloaded from MBF_PAR_INTELLIGENT_FILT_MIN_TIME.


Register 0x0421 - MBF_PAR_FILTRATION_STATE

Read-only. Current state of the filtration: 0 = off, 1 = on.

In MANUAL mode (MBF_PAR_FILT_MODE = 0), the state is set by writing to MBF_PAR_FILT_MANUAL_STATE.


Register 0x0422 - MBF_PAR_HEATING_DELAY_TIME

Internal timer in seconds that counts up when heating is due to be enabled. Once it reaches 60 seconds, heating is enabled. For internal use only.


Registers 0x0423-0x0424 - MBF_PAR_FILTERING_TIME_LOW and MBF_PAR_FILTERING_TIME_HIGH

Internal 32-bit timer for Intelligent filtration mode. Counts the total filtration time performed during a given day. For internal use only; should not be modified.


Registers 0x0425-0x0426 - MBF_PAR_INTELLIGENT_INTERVAL_TIME_LOW and MBF_PAR_INTELLIGENT_INTERVAL_TIME_HIGH

Internal 32-bit timer that counts the filtration interval assigned to Intelligent mode. For internal use only; should not be modified.


Register 0x0427 - MBF_PAR_UV_MODE

UV radiation disinfection mode. To enable UV support for a given device, add the mask MBMSK_MODEL_UV to the MBF_PAR_MODEL register.

Value Name Description
0 OFF UV is switched off and will not turn on when filtration starts
1 ON UV is switched on and will turn on when filtration starts; the UV lamp time counter will be incremented

Register 0x0428 - MBF_PAR_UV_HIDE_WARN

Suppression of UV mode warning messages:

Mask Name Description
0x0001 MBMSK_UV_HIDE_WARN_CLEAN Suppress cleaning warning
0x0002 MBMSK_UV_HIDE_WARN_REPLACE Suppress replacement warning

Register 0x0429 - MBF_PAR_UV_RELAY_GPIO

Relay number assigned to the UV function.


Register 0x042A - MBF_PAR_PH_PUMP_REP_TIME_ON

Time that the pH pump will be turned on in repetitive mode.

Bits Mask Description
0-14 0x7FFF Time value (see time coding below)
15 0x8000 MBMSK_PH_PUMP_REPETITIVE - if active, the pH pump operates in repetitive mode

Time coding: Covers periods of 1 to 180 seconds (1-second granularity) and 3 to 999 minutes (1-minute granularity). A value of ≤180 equals that many seconds. A value of >180: time in minutes = (value - 180 + 3). Example: value 200 → (200 - 180 + 3) = 23 minutes on.


Register 0x042B - MBF_PAR_PH_PUMP_REP_TIME_OFF

Time that the pH pump will be turned off in repetitive mode. No upper configuration bits. Uses the same time coding as MBF_PAR_PH_PUMP_REP_TIME_ON.


Register 0x042C - MBF_PAR_HIDRO_COVER_ENABLE

Configuration options for the hydrolysis/electrolysis module with cover detection:

Bit Mask Name Description
0 0x0001 MBMSK_HIDRO_COVER_ENABLE When active, hydrolysis production is reduced by the percentage in MBF_PAR_HIDRO_COVER_REDUCTION when the cover input is detected
1 0x0002 MBMSK_HIDRO_TEMPERATURE_SHUTDOWN_ENABLE When active, hydrolysis production stops when the temperature falls below the threshold in MBF_PAR_HIDRO_COVER_REDUCTION

Register 0x042D - MBF_PAR_HIDRO_COVER_REDUCTION

Configuration levels for cover reduction and hydrolysis shutdown temperature:

Bits Mask Name Description
0-7 0x00FF MBMSK_HIDRO_COVER_REDUCTION Percentage for cover reduction
8-15 0xFF00 MBMSK_HIDRO_SHUTDOWN_TEMPERATURE Temperature level for hydrolysis shutdown

Register 0x042E - MBF_PAR_PUMP_RELAY_TIME_OFF

Time in minutes or seconds that a dosing pump must remain off in temporized pump mode. Applies to all pumps except pH. Uses the same time coding as MBF_PAR_PH_PUMP_REP_TIME_ON.


Register 0x042F - MBF_PAR_PUMP_RELAY_TIME_ON

Time in minutes or seconds that a dosing pump must remain on in temporized pump mode. Applies to all pumps except pH. Uses the same time coding as MBF_PAR_PH_PUMP_REP_TIME_ON.


Register 0x0430 - MBF_PAR_RELAY_PH

pH regulation configuration:

Value Name Description
0 MBV_PAR_RELAY_PH_ACID_AND_BASE Device works with both acid and base pumps
1 MBV_PAR_RELAY_PH_ACID_ONLY Device works with acid pump only
2 MBV_PAR_RELAY_PH_BASE_ONLY Device works with base pump only

Note (v10.23 firmware): the same address 0x0430 is documented in the 2023 Hayward Vistapool spec under a different name and a substantially extended meaning — MBF_PAR_SETPOINT_MODE. In v10.23 this register encodes the regulation mode for all four measurement modules (pH, Redox/ORP, chlorine, conductivity) as a four-field bit-mask:

Bits Mask Identifier Module
0-2 0x0007 MBMSK_PAR_SETPOINT_MODE_PH pH
3-5 0x0038 MBMSK_PAR_SETPOINT_MODE_RX Redox / ORP
6-8 0x01C0 MBMSK_PAR_SETPOINT_MODE_CL Chlorine
9-11 0x0E00 MBMSK_PAR_SETPOINT_MODE_CD Conductivity

The 2015 MBV_PAR_RELAY_PH_ACID_AND_BASE (0), …_ACID_ONLY (1) and …_BASE_ONLY (2) values still match the lower three bits in v10.23, but v10.23 adds three further pH modes (MBV_PAR_SETPOINT_MODE_PH_ACID_BASE_SINGLE_REL = 3, …_HYST_NEG = 4, …_HYST_POS = 5) plus analogous mode tables for RX, CL, and CD. See docs/modbus-registers-v2023.md for the full enumeration.


Register 0x0431 - MBF_PAR_RELAY_MAX_TIME

Maximum time in seconds that a dosing pump can operate before raising an alarm. The behavior of the system when this time is exceeded is controlled by MBF_PAR_RELAY_MODE.


Register 0x0432 - MBF_PAR_RELAY_MODE

System behavior when the dosing time limit (set in MBF_PAR_RELAY_MAX_TIME) is exceeded:

Bits Mask Module
0-1 0x0003 pH
2-3 0x000C Rx (Redox)
4-5 0x0030 Cl (Chlorine)
6-7 0x00C0 Cd (Conductivity)
8-9 0x0300 Turbidity

Possible values for each field:

Value Name Description
0 MBV_PAR_RELAY_MODE_IGNORE The system ignores the alarm and dosing continues
1 MBV_PAR_RELAY_MODE_SHOW_ONLY The system shows the alarm on screen, but dosing continues
2 MBV_PAR_RELAY_MODE_SHOW_AND_STOP The system shows the alarm on screen and stops the dosing pump

Register 0x0433 - MBF_PAR_RELAY_ACTIVATION_DELAY

Delay time in seconds for the pH pump when the measured pH value is outside the allowable setpoints. The system internally adds an extra 10 seconds to the stored value. The pump starts dosing once the pH-out-of-range condition has been maintained for the configured time.


Registers 0x0434-0x04E7 - MBF_PAR_TIMER_BLOCK_BASE

A block of 180 registers holding the configuration of the 12 system timers. Each timer is assigned to a specific function:

Timer Base Register Assigned Function
0 0x0434 Filtration interval 1
1 0x0443 Filtration interval 2
2 0x0452 Filtration interval 3
3 0x0461 Auxiliary relay 1 - second interval
4 0x0470 Lighting interval
5 0x047F Auxiliary relay 2 - second interval
6 0x048E Auxiliary relay 3 - second interval
7 0x049D Auxiliary relay 4 - second interval
8 0x04AC Auxiliary relay 1 - first interval
9 0x04BB Auxiliary relay 2 - first interval
10 0x04CA Auxiliary relay 3 - first interval
11 0x04D9 Auxiliary relay 4 - first interval

Each timer block uses 15 registers:

Offset Name Description
0 OFFMB_TIMER_ENABLE Enables the timer in the selected working mode (see modes below)
1-2 OFFMB_TIMER_ON 32-bit timestamp (Low/High) that starts the timer
3-4 OFFMB_TIMER_OFF 32-bit timestamp (Low/High) that stops the timer (not used)
5-6 OFFMB_TIMER_PERIOD 32-bit time in seconds between starting points (e.g., daily = 86400)
7-8 OFFMB_TIMER_INTERVAL 32-bit time in seconds that the timer runs when started (e.g., 1 hour = 3600)
9-10 OFFMB_TIMER_COUNTDOWN 32-bit remaining time in seconds for countdown mode
11-12 OFFMB_TIMER_FUNCTION Function assigned to this timer (see function codes below)
13-14 OFFMB_TIMER_WORK_TIME Number of seconds the timer has been operating

Allowed timer working modes:

Value Name Description
0 CTIMER_DISABLE Timer disabled
1 CTIMER_ENABLED Timer enabled and independent
2 CTIMER_ENABLED_LINKED Timer enabled and linked to relay from timer 0
3 CTIMER_ALWAYS_ON Relay assigned to this timer always on
4 CTIMER_ALWAYS_OFF Relay assigned to this timer always off
5 CTIMER_COUNTDOWN Timer in countdown mode

Timer function codes:

Value Name Description
0x0001 CTIMER_FCT_FILTRATION Filtration function
0x0002 CTIMER_FCT_LIGHTING Lighting function
0x0004 CTIMER_FCT_HEATING Heating function
0x0100 CTIMER_FCT_AUXREL1 Auxiliary relay 1 function
0x0200 CTIMER_FCT_AUXREL2 Auxiliary relay 2 function
0x0400 CTIMER_FCT_AUXREL3 Auxiliary relay 3 function
0x0800 CTIMER_FCT_AUXREL4 Auxiliary relay 4 function
0x1000 CTIMER_FCT_AUXREL5 Auxiliary relay 5 function
0x2000 CTIMER_FCT_AUXREL6 Auxiliary relay 6 function
0x4000 CTIMER_FCT_AUXREL7 Auxiliary relay 7 function

Register 0x04E8 - MBF_PAR_FILTVALVE_ENABLE

Enables or disables the filter cleaning (backwash) functionality:

Value Description
0 Functionality disabled
1 Functionality enabled in Besgo mode

Register 0x04E9 - MBF_PAR_FILTVALVE_MODE

Valve timing mode:

Value Name Description
1 CTIMER_ENABLED Timed system - uses start time and period to schedule cleaning
3 CTIMER_ALWAYS_ON Cleaning activated manually; remains on for the duration set in MBF_PAR_FILTVALVE_INTERVAL
4 CTIMER_ALWAYS_OFF Filter cleaning is manually disabled and never activates

Register 0x04EA - MBF_PAR_FILTVALVE_GPIO

Relay assigned to the filter cleaning function (default: AUX2 = value 5):

Value Description
0 No relay assigned (filter cleaning function is inhibited)
1 pH relay
2 Filtration relay
3 Lighting relay
4 AUX1 relay
5 AUX2 relay (default)
6 AUX3 relay
7 AUX4 relay

Registers 0x04EB-0x04EC - MBF_PAR_FILTVALVE_START (32-bit)

32-bit timestamp (Low/High) marking the scheduled start time of filter cleaning.


Register 0x04ED - MBF_PAR_FILTVALVE_PERIOD_MINUTES

Period in minutes between filter cleaning actions. For example, a value of 60 means one cleaning action per hour.


Register 0x04EE - MBF_PAR_FILTVALVE_INTERVAL

Duration of the filter cleaning action in seconds.


Register 0x04EF - MBF_PAR_FILTVALVE_REMAINING

Remaining time of the current filter cleaning action in seconds. A value of 0 means no cleaning is in progress.

When a cleaning action starts, the value of MBF_PAR_FILTVALVE_INTERVAL is copied into this register and then decremented once per second. The display uses this register to show the progress of the cleaning function.


Register 0x04F0 - MBF_ACTION_COPY_TO_RTC

Special function register - use with extreme care. Writing to this register forces the values of MBF_PAR_TIME_LOW (0x0408) and MBF_PAR_TIME_HIGH (0x0409) to be written into the internal RTC microcontroller clock management registers.



2.6 User Page (USER)

All user page registers should be made persistent using MBF_SAVE_TO_EEPROM after modification.


Register 0x0500 - MBF_PAR_ION

Ionization target production level. The value set here must not exceed the factory maximum set in MBF_PAR_ION_NOM.


Register 0x0501 - MBF_PAR_ION_PR

Time in minutes that the ionization must be active each time filtration starts.


Register 0x0502 - MBF_PAR_HIDRO

Hydrolysis target production level. When operating in percent mode, this value is the percentage of production. When operating in g/h mode, this value is the desired production in g/h units.

The value must not exceed the factory maximum set in MBF_PAR_HIDRO_NOM.


Register 0x0504 - MBF_PAR_PH1

Upper limit (high setpoint) of the pH regulation system, multiplied by 100. Example: to set 7.50, write 750.

This register must always be higher than MBF_PAR_PH2.


Register 0x0505 - MBF_PAR_PH2

Lower limit (low setpoint) of the pH regulation system, multiplied by 100. Example: to set 7.00, write 700.

This register must always be lower than MBF_PAR_PH1.


Register 0x0506 - MBF_PAR_HIDRO_CTRL_MODULE

Documented in 2023 v10.23 (Hayward / Vistapool); not present in 2015 NeoPool spec.

This function determines which measurement module controls the hydrolysis generation.

Value Description
0 Hydrolysis generation is controlled by the ORP (RX) module
1 Hydrolysis generation is controlled by the chlorine (CL) module

Register 0x0508 - MBF_PAR_RX1

Redox/ORP regulation setpoint. Value must be in the range 0 to 1000.


Register 0x050A - MBF_PAR_CL1

Chlorine regulation setpoint, multiplied by 100. Example: to set 1.5 ppm, write 150. Value range: 0 to 1000.


Register 0x050E - MBF_PAR_CD1

Documented in 2023 v10.23 (Hayward / Vistapool); not present in 2015 NeoPool spec.

Lower set-point value for the conductivity module. Value is written in microsiemens. When the system is configured as dual set-point mode, this field contains the lower set point.


Register 0x050F - MBF_PUMP_CONFIG

Documented in 2023 v10.23 (Hayward / Vistapool); not present in 2015 NeoPool spec.

This register holds the configuration of the filtration pump. The register is divided into 5 different bit fields:

Bits Mask Description
0-3 0x000F Pump type. 0 = STANDARD, 1 = VARIABLE SPEED Type A, 2 = VARIABLE SPEED Type B
4-6 0x0070 Pump speed in manual mode: 0 = Slow, 1 = Medium, 2 = Fast
7-9 0x0380 Pump speed in filtration interval 1: 0 = Slow, 1 = Medium, 2 = Fast
10-12 0x1C00 Pump speed in filtration interval 2: 0 = Slow, 1 = Medium, 2 = Fast
13-15 0xE000 Pump speed in filtration interval 3: 0 = Slow, 1 = Medium, 2 = Fast

Example: value 0x0402 decodes as:

  • Pump type: 2 — Variable speed Type B
  • Manual mode: 0 — Slow
  • Filtration interval 1: 0 — Slow
  • Filtration interval 2: 1 — Medium
  • Filtration interval 3: 0 — Slow

Register 0x0511 - MBF_PAR_RX2

Documented in 2023 v10.23 (Hayward / Vistapool); not present in 2015 NeoPool spec.

Upper set-point for the redox regulation system. Used when the system is configured as dual set-point mode. Value range: 0 to 1000.


Register 0x0512 - MBF_PAR_CL2

Documented in 2023 v10.23 (Hayward / Vistapool); not present in 2015 NeoPool spec.

Upper set-point for the chlorine regulation system. Used when the system is configured as dual set-point mode. The value stored is multiplied by 100 (e.g. write 150 to set 1.5 ppm). Value range: 0 to 1000.


Register 0x0513 - MBF_PAR_PUMP_SPEEDS

Documented in 2023 v10.23 (Hayward / Vistapool); not present in 2015 NeoPool spec.

Pump speeds for specific actions when a variable-speed pump is configured.

Bits Mask Description
0-3 0x000F Speed used when operating the filtration valve: 0 = Slow, 1 = Medium, 2 = Fast, 3 = do not override
4-7 0x00F0 Speed used when operating cover protection: 0 = Slow, 1 = Medium, 2 = Fast, 3 = do not override
8-11 0x0F00 Speed used when operating the filtration valve: 0 = Slow, 1 = Medium, 2 = Fast

Register 0x051B - MBF_PAR_FUNCTION_DEPENDENCY

Function dependency specification - defines dependency of system functions on external events:

Bits Mask Name Description
0-2 0x0007 MBMSK_FCTDEP_HEATING Heating function dependency

Heating dependency bit values:

Bit Mask Name Description
0 0x0001 MBMSK_DEPENDENCY_FL1_PADDLE Heating depends on FL1 paddle switch
1 0x0002 MBMSK_DEPENDENCY_FL2 Heating depends on FL2
2 0x0004 MBMSK_DEPENDENCY_SLAVE Heating depends on slave input

Register 0x051D - MBF_PAR_PUMP_SCALING

Documented in 2023 v10.23 (Hayward / Vistapool); not present in 2015 NeoPool spec.

This register stores the pump scaling for the pH dosing pump and the other dosing pumps. The register is split in two fields, the lower one for the pH dosing timing and the upper for the rest of the pumps.

Bits Mask Description
0-7 0x00FF Pump scaling for the pH pump. Valid range: 0 (= 0 %) to 100 (= 100 %)
8-15 0xFF00 Pump scaling for the other pumps. Valid range: 0 (= 0 %) to 100 (= 100 %)

Scaling changes the pump-on time according to the difference between the set point and the currently measured parameter. The maximum scaling differences for each measurement module:

Module Difference
pH 1.0
Redox (ORP) 100 mV
Chlorine (Cl) 50 ppm
Conductivity (Cd) 500 microsiemens

Register 0x051E - MBF_PAR_CD2

Documented in 2023 v10.23 (Hayward / Vistapool); not present in 2015 NeoPool spec.

Upper set-point value for the conductivity module. Value is written in microsiemens. When the system is configured as dual set-point mode, this field contains the upper set point.


2.7 Miscellaneous Page (MISC)

This page contains registers associated with the display configuration and its visualization options.


Register 0x0600 - MBF_PAR_UICFG_MACHINE

Machine type, used to determine the title, colors, and units to display for hydrolysis/electrolysis:

Value Identifier Description
0 MACH_NONE No style assigned (default state after EEPROM erase)
1 MACH_HIDROLIFE Hidrolife style (yellow)
2 MACH_AQUASCENIC Aquascenic style (blue)
3 MACH_OXILIFE Oxilife style (green)
4 MACH_BIONET Bionet style (light blue)
5 MACH_HIDRONISER Hidroniser style (red)
6 MACH_UVSCENIC UVScenic style (lilac)
7 MACH_STATION Station style (orange)
8 MACH_BRILIX Brilix style
9 MACH_GENERIC Generic style (configure title and color separately)
10 MACH_BAYROL Bayrol style
11 MACH_HAY Hay style

When generic (9) is specified, the title and color registers described below must also be configured.


Register 0x0601 - MBF_PAR_UICFG_LANGUAGE

User interface language:

Value Language
0 Spanish
1 English
2 French
3 German
4 Italian
5 Portuguese (not implemented)
6 Turkish
7 Czech

Register 0x0602 - MBF_PAR_UICFG_BACKLIGHT

Screen backlight configuration, divided into two 8-bit halves:

Low byte (bits 0-7): screen timeout when no keys are pressed:

Value Timeout
0 15 seconds
1 30 seconds
2 60 seconds
3 5 minutes
4 Never turns off

High byte (bits 8-15): Backlight brightness percentage (10 to 100%).


Register 0x0603 - MBF_PAR_UICFG_SOUND

Sound alert configuration bitmask:

Bit Mask Description
0 0x0001 CLICK - a click sounds each time a key is pressed
1 0x0002 POPUPS - a sound plays each time a popup message appears
2 0x0004 ALERTS - an alarm sounds when there is an alert on the device (AL3)
3 0x0008 FILTRATION - an audible warning occurs each time filtration starts

Register 0x0604 - MBF_PAR_UICFG_PASSWORD

Equipment password encoded in BCD format.


Register 0x0605 - MBF_PAR_UICFG_VISUAL_OPTIONS

Visual options bitmask for user interface menus. Bits 0-7 hide normally visible options; bits 8-15 show normally hidden options:

Bit Mask Name Description
0 0x0001 HIDE_TEMPERATURE Hide temperature measurement
1 0x0002 HIDE_FILTRATION Hide filtration menu in main menu
2 0x0004 HIDE_LIGHTING Hide lighting menu in main menu
3 0x0008 HIDE_AUX_RELAYS Hide auxiliary relay adjustment menu in main menu
4 0x0010 MBMSK_VO_HIDE_EXTRA_REGS Hide additional register adjustment option in installer menu
5 0x0020 MBMSK_VO_HIDE_RELAY_CONFIG Hide relay configuration option in installer menu
6 0x0040 MBMSK_VO_SLOW_FILTER_HIDRO_LEVEL Enable slow filtering of the hydrolysis level when a pH module is installed (especially important when acid/base dosing is close to the hydrolysis probe)
7 0x0080 MBMSK_VO_HIDE_SALINITY_MAIN_WINDOW Hide salinity measurement on the main screen
8 0x0100 MBMSK_VO_SHOW_SPECIAL_REGS Show special registers configuration menu in installer menu
9 0x0200 SHOW_HID_SHUTDOWN_BY_TEMPERATURE Show hydrolysis shutdown by temperature option
10 0x0400 SHOW_CELL_SELECTION Enable access to cell selection menu from the service menu
11 0x0800 SHOW_PUMP_TYPE Show filtration pump type selection option (normal, three-speed, etc.)
12 0x1000 SHOW_QUICK_MENU Show quick access menu instead of conventional menu when SET is pressed from main display
13 0x2000 SHOW_OXI_MAIN_DATA_SCREEN Show main display screen in OXI style
14 0x4000 SHOW_INSTALLER_MENU Show installer menu in the main menu without requiring a password
15 0x8000 SHOW_FACTORY_MENU Show factory menu in the main menu without requiring a password

Register 0x0606 - MBF_PAR_UICFG_VISUAL_OPTIONS_EXT

Extended visual options bitmask:

Bit Mask Name Description
0 0x0001 MBMSK_VOE_SHOW_PNEUMATIC_VALVE Show the pneumatic valve option
1 0x0002 MBMSK_VOE_HIDE_AUX_REL_DEPENDENCY Hide auxiliary relay dependency option
2 0x0004 MBMSK_VOE_SHOW_BESGO_NAME Show "Besgo" instead of "Pneumatic" in pneumatic valve titles
3-15 Reserved

Register 0x0607 - MBF_PAR_UICFG_MACH_VISUAL_STYLE

Extension of registers 0x0600 and 0x0605.

Low byte (bits 0-7): Color/style for the generic machine type. Uses the same values as MBF_PAR_UICFG_MACHINE (0x0600).

High byte (bits 8-15): Supplementary configuration for hydrolysis display units:

Bit Mask Name Description
8-12 Reserved
13 0x2000 MBMSK_VS_FORCE_UNITS_GRH Force display of hydrolysis/electrolysis in grams per hour (g/h)
14 0x4000 MBMSK_VS_FORCE_UNITS_PERCENTAGE Force display of hydrolysis/electrolysis in percentage (%)
15 0x8000 MBMSK_ELECTROLISIS In generic mode, display the word "electrolysis" instead of "hydrolysis"

Logic for determining the hydrolysis display units:

  1. If MBMSK_VS_FORCE_UNITS_PERCENTAGE is set → display "%"
  2. Else if MBMSK_VS_FORCE_UNITS_GRH is set → display "gr/h"
  3. Otherwise, check machine type:
    • MACH_HIDROLIFE (1) or MACH_BIONET (4) → "gr/h"
    • MACH_GENERIC (9) with MBMSK_ELECTROLISIS set → "gr/h"
    • All other cases → "%"

Registers 0x0608-0x060B - MBF_PAR_UICFG_MACH_NAME_BOLD_0..3

Four registers storing an ASCIIZ string of up to 8 characters for the bold part of the startup title when machine type is set to generic.

Note: Only lowercase letters (a-z) may be used. Uppercase letters, symbols, and numbers are not allowed.


Registers 0x060C-0x060F - MBF_PAR_UICFG_MACH_NAME_LIGHT_0..3

Four registers storing an ASCIIZ string of up to 8 characters for the normal weight part of the startup title when machine type is set to generic.

Note: Only lowercase letters (a-z) may be used. Uppercase letters, symbols, and numbers are not allowed.