-[ ] Stream identifiers, APPIDs, VLANs, and configuration revisions match the engineering files.
43
+
44
+
## 4. Protocol observations
45
+
46
+
GOOSE:
47
+
48
+
-[ ]`stNum` increases only on state changes.
49
+
-[ ]`sqNum` behavior and retransmission intervals match the configured profile.
50
+
-[ ]`timeAllowedToLive` remains adequate for observed arrival gaps.
51
+
-[ ] Dataset values match the expected state transition.
52
+
53
+
Sampled Values:
54
+
55
+
-[ ]`smpCnt` progression and wrap policy match the configured sampling mode.
56
+
-[ ]`confRev`, `smpSynch`, `smpRate`, and optional `refrTm` are consistent.
57
+
-[ ] Missing, duplicate, and out-of-order sample counts are zero or explained.
58
+
-[ ]`seqOfData` channel mapping and scaling are validated against SCL, not inferred from byte position alone.
59
+
60
+
## 5. Escalation and evidence retention
61
+
62
+
-[ ] Save the PCAP, JSON report, SHA-256, SCL files, device configuration export, and test notes together.
63
+
-[ ] Record every mismatch before changing the parser or normalizing captured bytes.
64
+
-[ ] Do not enable active GOOSE/SV transmission from this stack until the receive-only evidence passes and a separate approved transmit test plan exists.
65
+
66
+
## Current status
67
+
68
+
The synthetic C#-derived corpus is automated in CI. Physical IED interoperability
69
+
remains **not yet passed** until a real capture and completed report are committed or
0 commit comments