C++ Port Status

Current milestone

Phase 4D-C5 — guarded IEC 61850 Smart Control is integrated for controlled laboratory interoperability: live ctlModel/TypeSpecification discovery, Direct/SBO normal and enhanced sequencing, exact Oper/SBOw/Cancel structures, CommandTermination correlation, LastApplError/AddCause diagnostics, and a read-only-by-default evidence harness.

The integration preserves Phase 4C live discovery and the Dynamic DataSet/reporting work already merged to main. Buffered-report recovery and ESP32 process-bus work remain separate concerns and are not used as evidence for MMS control behavior.

Delivered modules

Area Status
Phase 0 and Phase 1 process-bus foundation Merged to main
SCL and COMTRADE engineering formats Merged to main
TPKT/COTP and Session/Presentation/ACSE Merged to main
MMS Initiate and confirmed services Merged to main
Built-in Windows/Linux TCP transport Merged to main
Live read-only MMS discovery/model parity Merged to main
Dynamic DataSet lifecycle Merged to main
Guarded Dynamic RCB live-trial planner Merged to main
Guarded Direct/SBO control safety core Integrated from Phase 4D-C1 / PR #25
Live-type Oper/SBOw/Cancel MMS structure builder Integrated from Phase 4D-C2 / PR #27
CommandTermination and LastApplError/AddCause correlation Integrated from Phase 4D-C3 / PR #28
Live control discovery/session over MmsAssociationRuntime Integrated from Phase 4D-C4 / PR #29
Guarded physical interoperability harness and read-only inventory probes Integrated from Phase 4D-C5 / PR #30

Smart Control behavior

  • ctlModel values 0..4 match the C# oracle: status-only, Direct normal, SBO normal, Direct enhanced, and SBO enhanced.
  • Control roots are Data Objects (LD/LN.DO); service-leaf references are rejected as roots.
  • The control safety planner is association-aware and authorization is default deny.
  • ctlNum is monotonic in the range 1..255 and wraps to 1; zero is never auto-generated.
  • SBO retains an immutable selected sequence across ctlVal, origin, ctlNum, T, optional operTm, Test, synchrocheck, and interlock-check.
  • A second association cannot operate or cancel another association's selection.
  • Selection timeout, association loss, value/check mismatch, or authorization loss fail closed.
  • Direct normal and SBO normal complete at the accepted MMS service boundary.
  • Direct enhanced and SBO enhanced remain pending until a correlated CommandTermination arrives.
  • Ordinary ST/MX process reports cannot complete an enhanced command.
  • LastApplError retains raw ControlError/AddCause values while mapping the standard ControlError 0..3 and AddCause 0..27 names.
  • Positive Oper-only CommandTermination requires an exact CO/Oper reference.
  • Live TypeSpecification is authoritative for ctlVal, origin, ctlNum, T, Test, Check, and optional operTm; unknown vendor fields are rejected rather than guessed.
  • DPC uses MMS network bit order (Off=01, On=10).
  • Check is exactly two bits: bit 0 synchrocheck and bit 1 interlock-check.
  • Normal SBO Select is a Read of SBO; SBO enhanced SelectWithValue is exactly one SBOw Write.
  • Cancel is built from the exact retained selected sequence.
  • Stale InformationReports are drained before SBOw or Oper; reports arriving during the confirmed exchange remain available for application-error/termination correlation.
  • Missing CommandTermination expires as a control timeout and does not automatically fault an otherwise healthy MMS association.
  • No automatic command retry is performed.

C5 interoperability harness

ariec61850_control_interop_probe is the controlled live-test harness.

  • Read-only discovery is the default.
  • A control Write is rejected unless the exact --arm IEC61850-LAB-CONTROL token is supplied.
  • The operator must provide an explicit object, action, and typed value.
  • Supported actions are operate, select-operate, and select-cancel.
  • SPC, DPC, integer, unsigned, floating-point, and step-position values are bound conservatively from live type evidence.
  • Origin category/identifier, Test, synchrocheck, and interlock-check are explicit.
  • Live status is read before and after the action when the IED exposes a usable ST/MX reference.
  • Every control Write reference is counted and retained in JSON evidence.
  • JSON evidence includes ctlModel, CDC, status, Write count/list, report-observation counts, completion, MMS DataAccessError code/name, raw ControlError/AddCause, and mapped AddCause.
  • The tool prints a Wireshark MMS/TCP filter for JSON-to-PCAP reconciliation.
  • Offline --self-test verifies the read-only default and arm gate without network access.
  • A standalone CMake profile, Windows build helper, and cross-platform CI workflow are provided.

The laboratory procedure and evidence bundle are defined in docs/CONTROL_INTEROP_RUNBOOK.md.

Deterministic validation

Dedicated strict profiles cover:

  • GCC and Clang -fno-exceptions -fno-rtti guarded-control safety semantics;
  • default-deny authorization and revoked authorization between Select and Oper;
  • second-client takeover rejection, selection expiry, association-loss cleanup, Cancel ownership, and ctlNum wrap;
  • exact live-TypeSpecification control-value binding and golden MMS Data bytes for Oper;
  • DPC network bit order, StepPosition, and conservative analogue structures;
  • exact origin, ctlNum, T, Test, and two-bit Check construction;
  • LastApplError layouts, unknown raw-code preservation, and object correlation;
  • positive and negative enhanced CommandTermination behavior;
  • live descriptor discovery using ctlModel, GVAA, GetNameList, CF timeouts, and ST/MX status-reference priority;
  • Direct one-write behavior, SBO Select to Operate, SBOw asynchronous application-error handling, AutoSelect, stale-selection Cancel, and enhanced termination wait;
  • production MmsAssociationControlTransport strict compile validation;
  • integration of C1-C4 sources into the normal ARIEC61850::core build graph and CTest targets;
  • C5 harness offline safety gate and cross-platform build profile.

Physical interoperability acceptance

The software path and live harness are ready for controlled interoperability testing, but physical IED control acceptance is not claimed until retained evidence exists for:

  1. read-only live ctlModel and GVAA discovery for a known controllable object with mmsControlWriteCount=0;
  2. Direct normal Oper with exactly one command Write and observed process/status feedback;
  3. SBO normal SBO -> Oper plus explicit Cancel and selection-timeout behavior;
  4. Direct enhanced Oper -> CommandTermination positive and a safe negative LastApplError/AddCause path;
  5. SBO enhanced SBOw -> Oper -> CommandTermination plus ownership/contention behavior;
  6. association loss during selection and while waiting for enhanced termination;
  7. interlock/synchrocheck behavior only where the lab setup can exercise it safely;
  8. packet capture and JSON/event evidence proving no automatic command retry.

An individual profile may move from SOFTWARE_READY_FOR_LAB to LAB_INTEROP_PASSED only when its retained JSON and PCAP evidence agree.

Safety and claim boundary

  • Live inventory and raw ctlModel probes are read-only.
  • Mutating control requires explicit intent, an exact object root, live type discovery, and the harness authorization gate.
  • The implementation and deterministic tests are not an IEC 61850 conformance certificate.
  • No hosted CI result is treated as proof of a physical IED command.
  • Sampled Values, ESP32 hardware transmission, and BRCB persistence remain outside Smart Control acceptance.